AutoFlo S2020 User Manual
Page 7

7
A.
G.
B.
C.
D.
E.
F.
The green "Power" light does not blink off and on.
1. The S2000 is not connected to an active 120 
VAC 15 Amp power source. (S2020, 240 VAC,
10 AMP).
2. Call the Technical Support Hotline.
The "HEATER" LED does not illuminate.
1. The humidistat is not closed, calling for humidity or the 
humidistat is wired incorrectly.
 
2. The unit is in the maintenance cycle.
The HVAC Blower will not operate, but the "Blower" 
LED is on.
1. The blower "Field" wiring and/or interlock circuitry is 
incorrect.
2. The HVAC electric power is disconnected.
3.The humidifier internal "Blower" relay is defective. Call 
the Technical Support Hotline.
4. The HVAC Blower motor has failed.
The HVAC Blower will not operate and the "Blower" 
LED is not on.
1. The water pan temperature has not reached a high enough 
temperature to activate the "Blower" relay, about 170 
degrees Fahrenheit. This takes several minutes after the 
"HEATER" LED is illuminated. Depending on the water 
temperature and the surrounding condition, this may take 
up to 12 minutes. If the problem continues, the heater 
element may be defective, the thermistor temperature probe 
may be defective. Contact the Technical Support Hotline.
Red Service Light (error #1) is on constantly.
THERMISTOR ...This is an indication that the temperature 
probe is open or shorted to ground. May also indicate the 
probe has detected a pan temperature below 32 degrees F. 
Or in excess of 230 degrees F., resulting in a total shutdown. 
Try to reset the unit by unplugging the cord and 
reconnecting, or call Technical Support.
Red Service Light (error #2) is on constantly.
WATER ...This is an indication that the water fill time has 
been exceeded. The water level did not reach the probe tip 
in the given amount of time. It may also indicate an 
unsuccessful drain cycle. 
1. The water line is shut off at the saddle valve.
2. The water line is crimped or pinched.
3.The water valve inlet screen is plugged. Remove the 
water line from the unit and check the screen found inside 
the inlet side of the valve.
4.Unit is connected to a water source which is distilled, 
over-filtered, de-mineralized, or from a reverse osmosis 
system. Minimum 25 ppm water conductivity is 
required. 
*The unit supply water must contain dissolved
solids in the water, or the processor will not be able to 
detect the water level.
5.The water valve may be defective and must be replaced 
See replacement parts.
6. The drain valve is unplugged or defective.
7. Debris is clogging the drain valve or drain line.
8. Reset the unit by unplugging the power cord and re-
connecting.
Both Red Service Lights (error #3) are on.
HEATER FAILURE...This is an indication that the water 
temperature is not increasing or reaching the boiling 
point.
1. Faulty heater element or faulty wire connection.
2. This can happen if the unit is operated without water 
in the pan as a result of a water level probe malfunction, 
due to lack of maintenance. The pan boils dry and over-
heats the water pan. If this condition occurs, call the 
Technical Support Hotline.
3. The unit has operated for 45 minutes without a request 
for water, due to a leaking water fill valve, which is filling 
the tank continuously. 
If the humidifier seems to operate in a random manner 
that doesn't seem to fit any of the pre-described 
conditions, check the following:
1. Check to make sure that the wires used to connect the 
humidifier to the humidistat are separate wires and not 
part of a multi-wire bundle used to hook up the furnace 
thermostat or any other device. The associated close 
wires may create an induced voltage in the humidistat 
wiring.
2. Make sure that the water level probe and plastic 
insulator are clean and free of mineral build-up. It may 
become electrically conductive to ground, sensing a false 
indication that the water level is correct.
 
3. If the electric solenoid valve makes a loud noise when it 
closes, install an optional water hammer arrester to absorb 
the spike. Frequent or erratic water fill cycles can be due 
to air turbulence, when mounted in the supply air plenum.
4. The water probe uses the natural conductivity of the 
water, to determine the proper water level in the reservoir. 
Water that has been de-mineralized or over treated may 
not allow the unit to function properly. Minimum 25 ppm 
of total dissolved solids must be present in the water. 
Add approximately 1 tablespoon of salt to the tank, to 
temporarily remedy this problem.
5. These steam humidifiers must be connected to 
dedicated outlets of the proper current and voltage ratings. 
The use of extension cords is not recommended.
DO NOT cut off the grounded plug and/or 
hard wire this humidifier to line voltage. 
This will void the warranty.
H.
SERVICE INDICATORS