Campbell Scientific ST350 Strain Transducer for Structural Testing User Manual
Page 19

Section 5. Mounting of Sensor to Various Surfaces
-
Slide the drilling jig over the stud and align it with the second 
hole location. 
-
Drill the second 1/4” hole and follow the previous steps for 
securing the second concrete anchor. 
-
Remove the washers and nut from this stud.
-
Slide the transducer end over the stud without washers and the 
extension end over the one with washers. 
-
While holding the transducer assembly in place, screw nuts on the 
studs and tighten with an open-end wrench. 
3. Installation method for best measurements:
 
The method of gluing both tabs has been used for many years with very 
few problems. The main concern is having a clean, dust free surface for 
the glue to stick to. Occasionally the bottom of a slab may be wet or 
excessively rough, or the sensors must stay in place for over a couple of 
days, necessitating the use of mounting studs. Another consideration is if 
the structure has automobile or other traffic below it, it is always a good 
idea to use the studs on at least one end. 
-
Using two threaded studs is the most secure way to attach a 
transducer to an R/C structure, but it is considerably more time-
consuming and the accuracy of the marking and hole drilling is 
significantly more important. If the area is difficult to access, the 
transducers are going to be installed for an extended period of time, 
or it is imperative that the measurements be taken at a specific time, 
using two threaded studs is highly recommended. 
-
If the transducers are only going to be used for one day tab/glue is 
likely sufficient. If the transducer is going to be installed for two to 
four days the tab/glue + threaded stud is likely acceptable, but 
depends on the climate and concrete condition. In areas of high 
humidity the concrete tends to have higher moisture content. This 
moisture builds up behind the glue tab and in some cases can cause 
the tab to “pop” off. 
4. Pitfalls to avoid during installation:
-
If the Tab/Glue method is being used, ensure that the area is clean of 
dust before installing the gage. A can of compressed air or an air 
compressor is a great way to ensure a dust-free gluing area. 
-
If two threaded studs are going to be used, a drilling jig should be 
fabricated to properly locate the hole positions. The transducer does 
have an oval hole to help compensate for a hole being miss-drilled, 
but as the gage length increases, the variability in the alignment 
increases too. 
-
If the mounting surface is not flat or there are obstructions in the way 
of the extension, the obstruction may have to be chipped/ground or 
the mounting surface may need to be flattened with a grinder. 
5-5
