SS100 Sensor Simulator
Wiring
SS100
CR1000
Vin EX1
V1out 2H
V2out 2L
G
Multiplier and offset calculation:
Results with mult = 1, offset = 0, minimum depth = -177, maximum =
500. Assuming the range of the sensor is 0-100 feet, calculate the
multiplier and offset using equation of line; m = 0.15, offset = 26.14.
CRBasic measurement instruction:
BrFull (depth_ft,1,mv2500C,2,Vx1,1,2500,True ,True ,0,_60Hz,0.15,26.14)
CR1000 Water Level Pressure Transducer Simulation Example
'CR1000 Series Datalogger
'Declare Public Variables
Public depth_ft
'Define Data Tables
DataTable (SS100,true,-1)
DataInterval
(0,60,Sec,10)
Minimum
(1,depth_ft,FP2,0,False)
EndTable
'Main Program
BeginProg
Scan
(1,Sec,0,0)
'Bridge Measurement - Simulated Water Level
BrFull
(depth_ft,1,mv2500C,2,Vx1,1,2500,True
,True
,0,_60Hz,0.15,26.14)
'Call
Output
Tables
CallTable
SS100
NextScan
EndProg