Connection With External Supply
SDM-CD16AC
DATALOGGER
GND
12 V
C1 or SDM-C1 
C2 or SDM-C2 
C3 or SDM-C3 
Connection with Datalogger Supply
FIGURE 2. Connection Block Diagrams
If the 21X power supply is used to power the SDM-CD16AC, all low level 
analog measurements (thermocouples, pyranometers, thermopiles, etc.) must 
be made differentially. This is a result of slight ground potentials created 
along the 21X analog terminal strip when the 12 V supply is used to power 
peripherals. This limitation reduces the number of available analog input 
channels and may mandate an external supply for the SDM-CD16AC. 
4. Installation
• The SDM-CD16AC must be installed in an enclosure that provides a
pollution degree 2 environment (normally, only nonconductive pollution. 
However, a temporary conductivity caused by condensation may be 
expected). All Campbell Scientific enclosures meet this requirement. 
• Use copper conductors only. 
• Wire Range: 30 − 14 AWG 
• Tightening Torque: 5 − 7 in./lb. 
• Use minimum 60/75 degree C wire. 
• Input power must be connected to a class 2 supply only. All Campbell 
Scientific power supplies meet the class 2 supply requirements.