Campbell Scientific CD295 DataView II Dual Line Display User Manual
Page 26

DataView II (CD295) Dual Line Display
• Symptom
The DataView II displays ‘Waiting’ in a few (but not all) screens.
Explanation
This message indicates that the DataView requested a public variable from
the datalogger, but has not yet received a response.
If some screens function correctly, then the logger address, is correct,
and the datalogger is answering requests correctly.
Things to check
Is this the right version of the DataView program for the datalogger
program?
It is important that the program that is running in the datalogger is the
same as the one used when the DataView II program was written. If
not, then the DataView II program may need to be re-written.
• Symptom
After sending a program to the DataView II, it displays ‘No program’ and
won’t show any of my screens.
Explanation
The ‘No program’ message indicates that the current program in the
DataView II is incomplete or incorrect.
No permanent harm is done by sending an incorrect file, however it will
not execute.
Things to check
Did you download the correct file?
It is very important that you select the DV2 file that you created with
PC295, and not the 295 file which is only created for internal use by
the PC295 software itself, or any other file on your computer.
Try downloading again.
Could your DV2 file be corrupt?
No software other than PC295 should be used to edit DV2 files. Even
a slight change to the file is enough to cause the CD295 to reject the
program.
Try recreating the DV2 file in PC295, and download it again.
22