is set to 0 the detection/notification is disabled. Maximum value that can be 
entered is 640.00. 
 
Maximum Socket Lock Current: Is the value (in Amps) that when the branch 
circuit consumption is reached will lock all the OFF state sockets. To turn any of 
those sockets ON, the user must reduce the current consumption on the branch 
or increase this value. 
 
 
 
These are the configuration actions:
 
Format: Manufacturing initialization of the non-volatile storage for the 
configuration variables. This action will destroy any previous values that were 
saved. 
 
Set Defaults: Sets all the configuration variables to some pre-set default 
manufacturing values. 
 
Clear: Clears all the configuration variables. 
 
Reset Net: Makes effective the changes made to the network parameters. 
 
Save: saves all the displayed configuration data into the PowerScope’s non-
volatile storage and apply the newly configured values. 
 
Cancel: discards all the changes made in the current session. 
Load: shows all the current PowerScope configuration data.
 
 