Gateway: Contains the IP address of the network’s gateway PowerScope in the 
form of xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254. 
 
AutoIP: Check if the Inline Scope is having the IP address assigned by DHCP 
server. Not recommended. 
 
Host: Check if SNMP traps are to be sent to specific SNMP Host address. If 
checked, at least one of the 3 SNMP Host Addresses below has to be filled in. 
 
WEB: Check to enable standalone WEB GUI mode. 
 
SWU: Check to enable software update. 
 
SNMP Host Address: Contains the assigned IP address for the PowerScope in 
the form of xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254 of the Host(s) 
that the SNMP traps will be sent to. 
 
PDU Name: Name assigned to this PowerScope, the maximum number of 
characters that can be entered is less than 32. 
 
PDU Password: Holds the password used by the PowerScope to access SEMA. 
This is a protected variable accessible only by SEMA. 
 
SEMA Name: Name of the SEMA group that this PowerScope belongs to. This 
is a protected variable accessible only by SEMA. 
 
SEMA Password: Holds the password used by SEMA to access this 
PowerScope. This is a protected variable accessible only by SEMA. 
 
Min Temperature: Set the low temperature threshold (in degrees Fahrenheit) that 
when reached the PowerScope will send notification to SEMA over network. If 
this variable is set to 0 the notification is disabled. Maximum value that should 
be entered is 199. 
 
Max Temperature: Set the high temperature threshold (in degrees Fahrenheit) 
that when reached the PowerScope will send notification to SEMA over network. 
If this variable is set to 0 the notification is disabled. Maximum value that should 
be entered is 199. 
 
Min Humidity: Set the low humidity threshold (in %) that when reached the 
PowerScope will send notification to SEMA over network. If this variable is set to 
0 the notification is disabled. Maximum value that should be entered is 100. 
 
Max Humidity: Set the high humidity threshold (in %) that when reached the 
PowerScope will send notification to SEMA over network. If this variable is set to 
0 the notification is disabled. Maximum value that should be entered is 100. 
 
 
Maximum Current: Is the value (in Amps) that when the branch circuit 
consumption is reached the PowerScope will send alert to SEMA. If this variable 