Anchor  Bracket  

 

The  mounting  locations  for  the  anchor  brackets  are  shown  in  the  figure  below.  If  used  as  part  of  an  

aisle  containment  solution,  install  the  Floor  Seal  Kits  (P/Ns  39208-­‐XXX  and  39209-­‐XXX)  before  attaching  

the  anchor  brackets.  

 

 

Attach  the  cabinet  to  the  floor  with  3/8”  or  M10  hardware  appropriate  for  your  type  of  flooring.  

 

Bonding  the  cabinet  to  the  telecommunications  ground  

GF-­‐Series  GlobalFrame  Gen  2  Cabinets  should  be  bonded  to  the  telecommunications  ground.    The  top  

panel,  side  panels,  doors  and  mounting  rails  on  the  GlobalFrame  cabinet  are  electrically  bonded  to  the  

frame.    A  ground  strap  bonds  the  panels  and  doors  to  the  frame.    In  order  to  bond  the  cabinet  to  the  

telecommunications  ground,  use  the  Ground  Terminal  Block  (included)  to  connect  a  bonding  conductor  

to  the  telecommunications  ground  or  signal  reference  grid.    Remove  the  mask  sticker  at  desired  

grounding  location  and  apply  generous  coating  of  gray  antioxidant.  For  top  location,  remove  hole  plug  
and  route  wire  through  frame  top  first.    Secure  grounding  wire  to  the  terminal  block.    Attach  the  block  

to  the  cabinet  frame  with  an  8  mm  wrench  using  two  M5  bolts  and  nuts.