Chatsworth Products GF-Series GlobalFrame® Gen 2 Cabinet User Manual
Page 12
12
Anchor Bracket
The mounting locations for the anchor brackets are shown in the figure below. If used as part of an
aisle containment solution, install the Floor Seal Kits (P/Ns 39208-‐XXX and 39209-‐XXX) before attaching
the anchor brackets.
Attach the cabinet to the floor with 3/8” or M10 hardware appropriate for your type of flooring.
Bonding the cabinet to the telecommunications ground
GF-‐Series GlobalFrame Gen 2 Cabinets should be bonded to the telecommunications ground. The top
panel, side panels, doors and mounting rails on the GlobalFrame cabinet are electrically bonded to the
frame. A ground strap bonds the panels and doors to the frame. In order to bond the cabinet to the
telecommunications ground, use the Ground Terminal Block (included) to connect a bonding conductor
to the telecommunications ground or signal reference grid. Remove the mask sticker at desired
grounding
location
and
apply
generous
coating
of
gray
antioxidant.
For
top
location,
remove
hole
plug
and
route
wire
through
frame
top
first.
Secure
grounding
wire
to
the
terminal
block.
Attach
the
block
to the cabinet frame with an 8 mm wrench using two M5 bolts and nuts.