Symptom

Possible cause

Remedy

ON / OFF Switch is ON

• Switch is lighted

• There is no voltage at the at

the load end and the load is

shut down

• Voltage at the Load Terminals

(3, 4) is 13.8 ± 0.1V

• Voltage at Battery Terminals

(5, 6) is lower than the voltage

at the Load terminals and is

≤ 13.5 ± 0.2V

25A Fuse (F2) in the Load circuit is

blown due to:

- Excessive short time overload

current > 25A exceeding the

Time Current Characteristics of

the 25A fuse, or

-

Short circuit in the load circuit

Remove the cause of the overload

or short circuit

ON / OFF Switch is ON

• Switch is lighted

• Load is ON

• Voltage at the Load Terminals

(3, 4) is 13.8 ± 0.1V

• Voltage at Battery Terminals

(5, 6) is the same as the Load

Terminals (3, 4)

• Battery backup function does

not operate – Load shuts OFF
when AC power is interrupted

25A Fuse F1 in the battery circuit
is blown due to:

- Reversal of battery input

connections

- Short circuit in the battery

wiring

Check that the polarity of battery

connections is correct. Replace

the fuse.

Check for short circuit in the

battery wiring and correct.

GFCI outlet / GFCI breaker
supplying AC power to the unit
trips when the unit is switched
ON

Additional RF noise current from
the unit that is filtered to Earth
Ground increases the net Leakage
Current on the GFCI outlet / GFCI
breaker to > 5mA

Switch OFF other SMPS devices
operating from the same GFCI
outlet / GFCI breaker to reduce
the net leakage current to < 5mA.

Move the unit to another GFCI
outlet / GFCI breaker that has
lesser number of SMPS load(s) or
no SMPS load.

Power the unit from normal, non
GFCI outlet or from an outlet not
protected by GFCI breaker.

SeCtIOn 8 |

troubleshooting Guide