SeCtIOn 8 |

troubleshooting Guide

BAtteRY BAcKUP oPeRAtion - eXteRnAL BAtteRY iS connecteD

Symptom

Possible cause

Remedy

ON / OFF Switch is ON

• Switch is NOT lighted

• Load is ON and is operating

normally

• Output voltage at the Battery

Terminals (5, 6) is < 13.5 ±

0.2V and is dropping

• Output voltage at the Load

Terminals (3, 4) is 0.3V ± 0.1V

lower than the Battery Termi-

nals (5, 6) and is dropping

No AC power from the

AC outlet

Internal AC side fuse of the Power

Supply Section is blown

Check AC power is available at

the AC outlet. Breaker feeding

the AC outlet may have tripped.

Open the top cover and check

the 6.3A AC side fuse. Replace

if blown.

If the fuse blows again, the input

section is damaged. Please call

Tech Support.

ON / OFF Switch is ON

• Switch IS lighted

• Load is ON and is operating

normally

• Output voltage at the

Battery terminals (5, 6) is

<13.5V ± 0.2V and is dropping

• Output voltage at the Load

Terminals (3, 4) is 0.3 ± 0.1V

lower than the Battery Termi-

nals (5, 6) and is dropping

Power Supply Section of the Unit

has shut down due to over tem-

perature – Temperature of output

transformer windings is

≥ 105°C ± 5°C / 221°F ± 9°F.

Check that the fan is running. if

not, the fan / fan control circuit

may have been damaged. Call

Tech Support.

Check that the fan suction vents

on the sides of the unit and the

discharge vents on the bottom of

the unit are not blocked.

The Power Supply Section will

reset automatically when the

transformer windings cool down

to ≤ 75°C ± 5°C / 167°F

± 9°F. During the time the Power

Supply Section is OFF, the battery

will supply the load and will

discharge during this period.

ON / OFF Switch is ON

• Switch is lighted

• Load is ON

• Output voltage at the Load

Terminals (3, 4) loses regulation

and drops below 13.8 ± 0.1V

• Output voltage at the Load

Terminals (3, 4) is 0.3 ± 0.1V

lower than the Battery Termi-

nals (5, 6) and is dropping

Power Supply Section is over-

loaded and is in current limit

condition. The load is trying to

draw excessive current ≥ the cur-

rent limit value of 25A. The Time

Current Characteristic of the 25A

fuse (F2) in the Load circuit will

determine the allowable value of

overload current > 25A and the

time it can be sustained before

the fuse blows. The allowable

value will be higher for shorter

duration of overload.

Power Supply Section provides 25A

and the balance of current is fed

from the battery and the battery

starts discharging at current =

(Overload current - 25A)

Remove the cause of overload