Specifications – Clary SP1250 LE User Manual
Page 15
Page 15
SPECIFICATIONS
ELECTRICAL
Input
Voltage
120VAC 85VAC to 155VAC (without Battery discharge)
Frequency
45Hz to 65Hz
Output
Voltage
120VAC +3%
Frequency
50Hz or 60Hz +.25% (software selectable)
Current
SP560
SP1250LE
4.8 A (400W / 570VA)
10.4A (875W / 1250VA)
Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical
@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1
Harmonic Distortion
3%
Dynamic Response
+4% for 100% Step Load Change, 0.5 Millisecond Recovery Time
Overload
110% for 10 min; 200% for 50 milliseconds
Efficiency (UPS)
Load Power Factor
85%
0.7
UPS Protection
Input and Output Short Circuit; Input and Output Overload;
Excessive Battery Discharge
MECHANICAL
Input (Qty)
(1) IEC Inlet C14
Output (Qty)
SP560
SP1250LE
(1) IEC Outlet C13
(2) IEC Outlet C13
Overall Dimensions W x D x H
SP560
SP1250LE
11in x 8.5in x 1.7in
15.25in x 8.5in x 1.7in
Weight
SP560
SP1250LE
5 lb. (2.3 kg)
8 lb. (3.6 kg)
Cooling
Low Velocity, Forced Air
CONTROLS AND INDICATORS
Visual Indicators
Battery Status, AC Output, Alarm, AC Input
Controls
Load On/Off, Cold Start
Intelligent Computer Interface
(1) DB9-F – RS232/Signal Interface
(1) USB Type B
DESIGN
Standard Features
Regenerative On-Line, Sinewave Inverter Powers Load Continuously,
Extended Brownout Protection, External Battery Connector, Digitally
Controlled IGBT PWM, Power Factor Corrected on Input, Designed for
Non-linear Loads
ENVIRONMENTAL
Operating Temperature
-40
o
F to 165
o
F (-40
o
C to 74
o
C)
Humidity
0% to 95% non-condensing
Altitude
Sea Level to 10,000 Feet