Technical data venting, table 3 – State SBD100 399NE A User Manual

Page 11

background image

11

MODEL 120
Input: 120,00Btuh

Total Vent Height (Feet)

Draft Hood: 5”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (inches)

120,000

1 Ft.

7

7

7

6

6

6

6

6

120,000

2 Ft.

6

6

6

6

6

6

6

5

123,000

3 Ft.

6

6

6

6

6

5

5

5

Number

Combined Input

of Heaters

in Thousands of Btuh

Manifold and Common Vent Diameter (In inches)

2

240

10

8

8

7

7

7

6

7

3

360

10

10

10

10

8

8

7

7

4

480

12

12

12

10

10

10

8

8

MODEL 154
Input: 154,000 Btuh

Total Vent Height (Feet)

Draft Hood: 6”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (in inches)

154,000

1 Ft.

8

8

7

7

7

7

7

7

154,000

2 Ft.

7

7

7

7

7

6

6

6

154,000

3 Ft.

7

7

7

6

6

6

6

6

Numbers

Combined Input

of Heaters

in Thousands of Btuh

Manifold and Common Vent Diameter (in inches)

2

308

10

10

10

8

8

7

7

7

3

462

12

12

12

10

10

10

8

8

4

618

14

14

12

12

12

10

10

10

MODELS 180, 197, 198, 199, 200
Input: 180,000, 190,000, 199,000 Btuh

Total Vent Height (Feet)

Draft Hood: 6”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (in inches)

180,000

1 Ft.

8

8

8

8

8

7

7

7

190,000

-

8

8

8

8

8

7

7

199,000

-

-

8

8

8

8

8

7

180,000

2 Ft.

8

8

7

7

7

7

7

7

190,000

8

8

8

7

7

7

7

7

199,000

8

8

8

8

7

7

7

7

179,000

3 Ft.

7

7

7

7

7

7

6

6

190,000

8

7

7

7

7

7

6

6

197,000

8

7

7

7

7

7

7

6

199,000

8

8

7

7

7

7

7

6

Number of

Combined Input

Heaters

in Thousands of Btuh

Manifold & Common Vent Diameter

358

10

10

10

10

8

8

7

7

2

380

12

10

10

10

10

8

7

7

394/398

12

10

10

10

10

8

8

7

537

14

12

12

12

10

10

10

8

3

570

14

12

12

12

10

10

10

10

591/597

14

14

12

12

12

10

10

10

716

14

14

14

12

12

12

10

10

4

760

16

14

14

14

12

12

10

10

788/796

16

14

14

14

12

12

12

10

TYPE B GAS VENT

Multiple Gas Fired Tank-Type Heaters

When venting mutiple tank type heaters using Type B
vent pipe, follow the installation diagram (figure 8) and
tables below which give sizing and data based upon
NFPA 54/ANSI Z223. 1992.

TECHNICAL DATA VENTING, TABLE 3