Water Supply Systems, ANSI Z21.22 - current edition. This
valve must be marked with the maximum set pressure not
to exceed the marked maximum working pressure of the
water heater. Install the valve into an opening provided and
marked for this purpose in the water heater, and orient it or
provide tubing so that any discharge from the valve exits
only within 6 inches above, or at any distance below, the
structural fl oor, and does not contact any live electrical part.
The discharge opening must not be blocked or reduced in
size under any circumstance.
IMPORTANT: Only a new temperature and pressure relief

valve should be used with your water heater. Do not use an

old or existing valve as it may be damaged or not adequate

for the working pressure of the new water heater. Do not

place any valve between the relief valve and the tank.

The Temperature & Pressure Relief Valve:

Shall not be in contact with any electrical part.

Shall be connected to an adequate discharge line.

Shall not be rated higher than the working pressure
shown on the data plate of the water heater.

The Discharge Line:

Shall not be smaller than the pipe size of the relief
valve or have any reducing coupling installed in the
discharge line.

Shall not be capped, blocked, plugged or contain
any valve between the relief valve and the end of the
discharge line.

Shall terminate a maximum of 6 inches above a floor
drain or external to the building. In cold climates, it is
recommended that the discharge pipe be terminated at
an adequate drain inside the building.

Shall be of material listed for hot water distribution.

Shall be installed to allow complete drainage of both
the valve and discharge line.

Solar Installation

If this water heater is used as a solar storage heater or
as a backup for the solar system, the inlet water supply
temperatures to the water heater tank may be in excess of
120°F. A mixing valve or other temperature limiting valve
must be installed in the inlet water supply line to limit the
supply temperature to 120°F.

NOTE: Solar water heating systems can often supply water
with temperatures exceeding 180°F and may result in water
heater malfunction.

Water Heater Location

Centrally located with the water piping system.

Located indoors and in a vertical position. Protected

from freezing temperatures.

Provisions made to protect the area from water

damage. A suitable drain pan installed and piped to an
adequate drain.

Sufficient room to service the water heater.

Water System Piping

Temperature and pressure relief valve properly

installed with a discharge line run to an open drain
and protected from freezing.

All piping properly installed and free of leaks.

Heater completely filled with water. (See Figure 2)

Closed system pressure buildup precautions

installed.

Mixing valve (when applicable) installed per

manufacturer’s instructions (see “Water Temperature
Regulation” section).

Electrical Connections

Wiring and connections comply with all applicable

codes.

Water heater and electrical supply are properly

grounded.

Proper overload fuse or circuit breaker protection

installed.

INSTALLATION
CHECKLIST