5

Electrical Requirements

If you lack the necessary skills required to properly install

the electrical wiring to this water heater, do not proceed but

have a qualifi ed electrician perform the installation.
When making the electrical connections, always make

sure:

The electrical supply has the proper overload fuse or

breaker protection.

Wire sizes and connections comply with all applicable

codes.

Wiring enclosed in approved conduit (if required by

local codes).

The water heater and electrical supply are properly

grounded.

Figures 3, 4, and 5 are provided as reference drawings

for the 120/240v 2-wire models only. Always reference

the wiring diagram located on the water heater for the

correct electrical connections and connect the electrical

supply to the water heater in accordance with local utility

requirements and codes.
When installing the electrical wiring to the water heater:
1. Be sure tank is completely filled with water before

making any electrical connections. (See Figure 2)

2. Disconnect the electric power.
3. Loosen the screw holding the junction box cover to the

top of the water heater and set aside.

4. Connect the electrical supply to the water heater.

A standard 1/2 inch opening has been made in the

junction box for conduit connections.

5. Connect ground wire to green ground screw in the

junction box of the water heater. Reinstall the junction
box cover.

Figure 3
120/240V 2-Wire Models

Junction Box

Cover

Ground

Wire

Conduit

White Wire (120V Models)

Red Wire (240V Models)

Black Wire

Green

Ground

Screw

Black

White

Approved Connectors

Figure 4

Wiring Diagram

120V Models Only

Overload

Protection

Neutral

Hot

Circuit

Breaker

To 120V

Power Supply

Electrical

Service Ground

Ground

Screw

Black

Red

Approved Connectors

Figure 5
Wiring Diagram

208/240v Models Only

Overload

Protection

To 208/240v

1 Phase

Power supply

Electrical

Service ground

L1

L2

Circuit

Breaker

Ground

Screw

NOTE: Applying electrical power to elements that are not submerged
in water will destroy them. The manufacturer will not warranty any
elements damaged in this manner.

Figure 2
Heating Element

WARNING

Electric Shock Hazard

Disconnect power before
servicing.

Replace all parts and panels
before operating.

Failure to do so can result in
death or electrical shock.

WARNING

Fire Hazard

Use proper size solid copper
wire.

Use a UL listed or
CSA approved strain relief.

Connect ground wire to green
ground screw.

Failure to do so can result in
death, fire, or electrical shock.