beautypg.com

Troubleshooting guidelines – State GS6 75 YRPDT User Manual

Page 31

background image

31

TROUBLESHOOTING GUIDELINES

TROUBLESHOOTING GUIDELINES

TROUBLE SHOOTING

Please check guidelines below. For your safety, water heater service should be performed only by a qualifi ed service technician.

Read the GENERAL SAFETY INFORMATION section fi rst.

#

LED STATUS

PROBLEM

SOLUTION

1

The gas control valve/thermostat
has sensed inadequate or no earth
ground.

1 Ensure the wall outlet (power supply) is properly

grounded.

2 Ensure all ground connections/wires on the water

heater are securely connected.

2

The gas control valve/thermostat
has sensed reversed polarity in the
120 VAC power supply.

1 Ensure the wall outlet/power supply is properly wired.

2 Ensure all internal 120 VAC wiring connections and

wiring harness have no reversed wires. 120 VAC "hot"
wire must connect to the on/off switch.

3

Pressure switch circuit remaining
closed for more than 5 seconds
after heating cycle begins.

Blower may not start in this
condition.

1 Ensure air pressure switch circuit wiring is correct and

the air pressure switch is not jumpered.

2 Replace the air pressure switch.

4

Pressure switch circuit remains
open longer than 5 seconds after
the blower is energized.

Blower may run continuously in
this condition.

1 Ensure the air pressure switch sensing tube is properly

connected at both ends and is not kinked or damaged.

2 Ensure the correct size of vent and intake air pipe (direct

vent products) was used per the installation instructions
in the manual that came with the water heater.

3 Ensure maximum number of elbows or maximum

equivalent feet of vent or intake air pipe has not been
exceeded per the installation instructions in the manual
that came with the water heater.

4 Ensure there are no obstructions in the vent or intake air pipe.

5

The gas control valve/thermostat
has detected an open igniter circuit.

1 Check wiring to the hot surface igniter assembly -

replace igniter assembly if wiring is damaged or worn.

2 Check resistance of the igniter at igniter assembly

plug - should be between 11 and 18 ohms at room

temperature (77° F at plug end) - replace igniter if open

or shorted.

3 Check igniter assembly plug and the socket on the gas

control valve/thermostat for good connection.

4 Replace igniter assembly if the plug is worn or damaged.

5 Replace the gas control valve/thermostat if the igniter

assembly socket on the bottom of the control is worn or

damaged.

6

Ignition/fl ame failure.

The gas control valve/thermostat
has reached the maximum number
of retries (3) for ignition and is
currently locked out for one hour.

Cycle the power to the water heater
off and on to reset.

1 Ensure fl ame sensor is making good contact with the

burner fl ame and ensure fl ame is steady. Also ensure

supply and manifold gas pressures are within the

requirements in the installation manual.

2 Gas supply is turned off - pressure is too low.

3 Ensure the fl ame sensor is clean - use fi ne steel wool

to clean the fl ame sensor.

4 Check igniter assembly plug and the socket on the

bottom of the gas control valve/thermostat for good

connection. Replace igniter assembly if the plug is worn

or damaged. Replace the gas control valve/thermostat if

socket is worn or damaged.

5 Replace igniter assembly.

This manual is related to the following products: