Grounding Instructions

The FW-X240’s metal mounting bracket must be connected to a permanently grounded

system. System grounding as required by the National Electric Code, ANSI /NFPA 70-1996, is the

responsibility of the system installer.

• The FW-X240 hardware kit includes grounding washers to penetrate a powder-coated fi nish,

assuring a proper ground connection to any FLEXware enclosure or mounting plate.

• An installation might call for an optional grounding wire between the FW-X240 and the FLEXware

enclosure or mounting plate to which it’s attached depending on local code requirements or the

nature of the installation itself.

Connections

• No additional terminals or lugs are required for hook-up of the AC wiring.

• AC wiring must be no less than 10 AWG gauge copper wire, rated for 75 degrees C or higher and

must be sized appropriately to the circuit breaker.

Hardware Kit

The FW-X240 comes with four M6 X 20 mm screws, four fl at washers, and four grounding washers for

mounting to a FLEXware Mounting Plate from inside a FLEXware AC enclosure.