American Fibertek MRX-8885C User Manual
Page 11

11
OFFSET BIAS – RS485
The RS485 specification requires receivers to detect input signals down to 200mVp-p of voltage 
level. In many cases this can cause systems to be sensitive to noise on the data wires. In an 
effort to eliminate the effects of low levels of noise, some manufacturers of equipment that 
communicate using RS485 have introduced a small voltage bias to the data lines. This is 
usually accomplished using a 470 Ohm resistance to +5V on the positive line and 470 Ohm 
resistance to ground on the negative line. When used in conjunction with the appropriate 
termination resistors referred to in the previous section, this introduces about a 300 mV offset, 
improving noise immunity. 
 
Offset bias for four wire RS485 can be applied on the MTX-8885C and MRX-8885C by setting 
switch # 1 and switch # 3 down. Please note that these switches work as a set and must be 
either both down or both up. In a majority of cases, bias will not be required and these switches 
should remain in the up position. If using offset bias, it is important that termination resistor 
switch # 2 and switch # 5 be in the down (applied) position. Using offset bias without a 
termination on the line will cause communications to fail. 
 
Offset bias for two wire RS485 can be applied on the MTX-8885C and MRX-8885C by setting 
switch # 4 and switch # 6 down. Please note that these switches work as a set and must be 
either both down or both up. In a majority of cases, bias will not be required and these switches 
should remain in the up position. If using offset bias, it is important that termination resistor 
switch # 5 be in the down (applied) position. Using offset bias without a termination on the line 
will cause communications to fail. 
