Control system components – American Standard CH530 User Manual
Page 60

CDHF-SVU01C-EN
60
Control System
Components
GBAS (Generic Building Automation System)
1A15 Optional Dual
GBAS
Signal #1
Percent RLA Compressor Output
J2-1 Output #1, J2-3 Ground
Analog Input/
output Module
1A16 Optional Dual
GBAS
Signal #1
External Current limit Setpoint
J2-2 Input #1, J2-3 Ground
Analog Input/
output Module
1A16 Optional Dual
GBAS
Signal #2
Chilled Water Reset input,
J2-5 Input #2, J2-6 Ground
Analog Input/
or External Chiller Water Setpoint
output Module
Percent RLA Output
2 to 10 Vdc corresponding to 0 to
120% RLA. With a resolution of
0.146%. The Percent RLA Output
connections are on the terminals
1A15 –J2-1 (+) to J2-3 (Ground). The
Percent RLA Output is polarity
sensitive.
The following graph illustrates the
output:
Figure 27. Voltage versus percent RLA