IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact

the factory.

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the left side panel area behind the top control (access) door. In the case of
208 VAC OR 230/240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.

IMPORTANT: The wire size must be properly sized to handle the related current.

WARNING: 208 VAC AND 230/240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or

obligation.

EURO-12 (Gas)

EURO-12 (Steam)

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.


B.


C.

208 VAC AND 240 VAC

ARE NOT THE SAME. When

ordering, specify exact voltage.

When fuses are used they

must be dual element, time delay, current

limiting, class RK1 or RK5

ONLY. Calculate/determine correct fuse

value, by applying either local and/or National Electrical Codes to listed

appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type

ONLY. For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.

Circuit breakers for 3-phase (3Ø) dryers

must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

120

2

10

--

20

208

2

5

--

15

240

2

5

5

15

208

3/4

3

--

15

240

3

3

4

15

380-400

3/4

--

2

15

416

3/4

--

2

15

460/480

3/4

2

--

15