Specifications

Input conductors

This product is rated 200 A. It should be supplied with a circuit breaker
with a maximum rating of 200 A.

For North America, if supplied by a 200 A circuit breaker, it is
recommended that conductors are sized in accordance with Table 3.

For countries outside of North America, if supplied by a 200 A circuit
breaker, it is recommended that conductors are sized in accordance with
Table 4.

Note: Input conductors are to be torqued to 31.1 Nm
(275 lb-in) using a 8 mm (5/16 in) Allen (hexagonal) wrench.

Table 1

Table 2

Table 3

Notes
CCC = Current-Carrying Conductors
AWG = American Wire Gauge
kcmils = MCM = Thousands of Circular Mils
Ø = Phase conductor
N = Neutral conductor
G = Ground (Equipment Grounding) conductor
(2) = two conductors per terminal

Table 4

Notes
Ø = Phase conductor
N = Neutral conductor
PE = Protective Earth conductor
PVC = Polyvinyl-chloride
XLPE = Cross-linked polyethylene
EPR = Ethylene propylene rubber

AC Input

Nominal voltage

400 V 3 PH
208 V 3 PH

Frequency

47-63 Hz

Voltage configuration

3 W + N + PE

Maximum upstream circuit breaker

200 A

Maximum continuous current

160 A

Maximum continuous current with
100% rated circuit breaker

200A

Maximum main input conductor size

250 mcm

AC Output

Nominal voltage

230 V/400 V 3 PH
120 V/208 V 3PH

Maximum continuous current

200 A

Voltage configuration

3 W + N + PE or 3 x (1 W + N + PE),
based on attached APC Power
Distribution Modules

Full load rating

138 kW @ 400 V 3PH
72 kW @ 208 V 3 PH

Output power cable connections

Various, based on attached APC Power
Distribution Modules

Output power cable lengths

Various, based on attached APC Power
Distribution Modules

Maximum APC Power Distribution
Modules

6

Maximum power distribution poles

18

200 A, 75°C Conductors

Wiring System

Copper

Aluminum

3 CCC, 30°C Ambient Ø&N = 3/0 AWG

G = 6 AWG

Ø&N = 4/0 AWG
G = 4 AWG

4 CCC, 30°C Ambient Ø&N = 4/0 AWG

G = 6 AWG

Ø&N = (2) 1/0 AWG
G = (2) 4 AWG

200 A, Conductors

Install.

Method

Copper, PVC
Insulation,

30°C Ambient

Copper, XLPE

or EPR
Insulation,

30°C Ambient

Aluminum,
PVC Insulation,

30°C Ambient

Aluminum,

XLPE or ERP
Insulation,

30°C Ambient

B1

Ø&N = 95 mm²
PE = 50 mm²

Ø&N = 70 mm²
PE = 35 mm²

Ø&N = 150 mm²
PE = 95 mm²

Ø&N = 95 mm²
PE = 50 mm²

B2

Ø&N = 120 mm²
PE = 70 mm²

Ø&N = 95 mm²
PE = 50 mm²

Ø&N = 240 mm²
PE = 120 mm²

Ø&N = 120 mm²
PE = 70 mm²

C

Ø&N = 95 mm²
PE = 50 mm²

Ø&N = 70 mm²
PE = 35 mm²

Ø&N = 150 mm²
PE = 95 mm²

Ø&N = 95 mm²
PE = 50 mm²

E

Ø&N = 95 mm²
PE = 50 mm²

Ø&N = 70 mm²
PE = 35 mm²

Ø&N = 120 mm²
PE = 70 mm²

Ø&N = 95 mm²
PE = 50 mm²

F

Ø&N = 70 mm²
PE = 35 mm²

Ø&N = 50 mm²
PE = 25 mm²

Ø&N = 95 mm²
PE = 50 mm²

Ø&N = 70 mm²
PE = 35 mm²