beautypg.com

11 control nozzle, 12 control probe, 13 chilled water manifold – Sterlco S Series Central Chilling Stations User Manual

Page 32: 14 optional condenser water manifold

background image

Page 32 of 77

SCW Series Central Chilling Stations

4-11 Control Nozzle

All SCW Series chilling station evaporators have two control
nozzles. The flow switch, freezestat, and flush port are located in
the control nozzle. Pressure gages are mounted in the control
nozzles to aid in achieving proper flow through the evaporator and
balancing flows.

Pressure drop between evaporator entering water pressure and
evaporator leaving water pressure can be converted to gallons per
minute using the pressure drop charts below.

Water Side Pressure Drop

Condenser (each)

Evaporator (each)

Model

Number

Flow (gpm)

PD (psi)

Flow (gpm)

PD (psi)

SCWW/R60 91

4.0 72

5.3

SCWW/R75 102

4.7

90

4.5

SCWW/R90 117

4.4

107

5.6

SCWW/R100 150

5.5

123

3.9

SCWWR115 166

4.3

140

3.0

SCWW/R145 196

4.1

175

4.8

SCWW/R165 219

4.1

200

4.6

SCWW/R195 278

4.7

232

6.0

4-12 Control Probe

Two control probes sense temperatures. One probe measures the
temperature of the hot well and the other does the same for the
cold well of the reservoir. These temperatures are used by the PLC
controller to sequence the compressors, based on load.

4-13 Chilled Water Manifold

The chilled water manifold allows one-point connections of

TO

PROCESS

piping. The Sch. 40 steel piping includes butterfly

valves at each evaporator for flow balancing and circuit isolation;
optional pressure gauges can be installed.

4-14 Optional Condenser Water Manifold

The optional condenser water manifold allows one-point
connection of

TO TOWER

(drain) and

FROM TOWER

(city water)

piping. Sch. 40 steel include butterfly valves for each condenser.