Chilled Water Pump Tanks
American Standards
Maximum
tons
Return
Tank
weight
chilled
H
2
O
c Capacity Maximum
water
&
overflow
Dimensions (less
pumps)
Model Single
Dual
gallons
Pumps/
Connections
inches
pounds
number well
well
Overflow
Operating
Ledge inches L W H
Shipping
Operating
CW140 (D)
47
23
125
110
3
3” NPT
72
36
40
600
1,800
PC390 (D)
d
146 73 390 350
3
ℜ 5” CLMP
95 56 64
500
3,500
CW480 (D)
175
87
450
420
3
4” FLG
102
49.5
52
2,000
6,000
CW720 (D)
262
131
675
630
4
4” FLG
114
73.5
52
2,600
8,600
CW1080 (D)
411
206
1,030
990
4
6” FLG
114
73.5
77
3,400
12,400
CW1620 (D)
617
309
1,550
1,480
4
6” FLG
138
73.5
77
4,000
17,500
CW2040 (D)
771
386
1,910
1,850
5
6” FLG
150
91
78
5,000
22,100
CW2700 (D)
1,029
514
2,545
2,470
6
6” FLG
150 121
78
6,000
28,500
CW3670 (D)
1,418
709
3,490
3,405
6
6” FLG
162 121
90
7,000
37,600
CW5130 (D)
1,985
993
4,890
4,765
7
ℜ 8” FLG
162 169
92
7,800
50,700
CW6285 (D)
2,553
1,276
6,285
6,125
9
ℜ 10” FLG
162 217
94
14,700
69,100
c Based on 2.4 gpm per ton.
d “P” signifies molded polyethylene tank.
ℜ PC390 = 6” CLMP, CW5130 = 6” FLG, CW6285 = 8” FLG overflow connections only.
Metric Standards
Maximum
cooling,
Return
Tank
weight
chilled
H
2
O
c Capacity
Maximum
water
&
overflow
Dimensions (less
pumps)
Model Single Dual
liters
pumps/
connections
cm
Kg
number well well
Overflow
Operating
ledge mm L
W
H
Shipping Operating
CW140 (D)
177,876
87,046
473
416
3
76 mm
183
91 102
273
817
PC390 (D)
d
552,552 276,276 1,476
1,325
3
ℜ 127 mm 241
142 162
227
1,588
CW480 (D)
662,305
329,260
1,703
1,590
3
102 mm
259
126 132
908
2,722
CW720 (D)
991,565
495,783
2,555
2,385
4
102 mm
289
187 132
1,180
3,901
CW1080 (D)
1,555,471
779,628
3,849
3,747
4
152 mm
289
187 195
1,543
5,625
CW1620 (D)
2,335,098 1,169,441
5,867
5,602
4
152 mm
350
187 195
1,815
7,938
CW2040 (D)
2,917,927 1,460,856
7,229
7,002
5
152 mm
381
231 198
2,268
10,025
CW2700 (D)
3,894,353 1,945,284
9,633
9,349
6
152 mm
381
307 198
2,722
12,928
CW3670 (D)
5,366,263 2,683,281
13,209
12,888
6
152 mm
411
307 229
3,176
17,056
CW5130 (D)
7,512,431 3,758,108
18,509
18,036
7
ℜ 203 mm 411
429 234 3,539
22,998
CW6285 (D)
9,662,084 4,829,150
23,789
23,183
9
ℜ 254 mm 411
551 239 6,668
31,344
c In Kcal/hr, calculated for chilled water, based on 3 lpm per 1,000 Kcal/hr.
d “P” signifies molded polyethylene tank.
ℜ PC390 = 152mm, CW5130 = 152mm, CW6285 = 203mm overflow connections only.
Top View
Front View
Side View
(P2 Pump S hown Only For Clarity)