Troubleshooting


Ensure all tests are undertaken by a qualified, trained engineer
Ensure safe working practices are followed at all times

Step 1 Basics

Check polarity of illuminator connection: red= +ve, black= -ve

Ensure PSU outputs provide 24V DC

Ensure telemetry wires are shorted out or closed contact input (zero volt) is applied

Check photocell is working. Cover illuminator photocell fully, light should turn on. It is

sometimes difficult to see Infra-Red lamps working in high brightness conditions.

Check mains input

Check fuses intact

If longer cables used, ensure sufficient voltage is provided to allow for drops across the

cable


If OK…

Step 2 Lamp Test

Check current is being drawn

– amount of current will depend on power setting of

unit. Please note

– use appropriate DC multimeter

To test this you must ensure photocell fully covered (or disabled using optional VARIO

remote controller or VARIO IP web interface) and ensure telemetry wires are shorted out
or closed contact input (zero volt) is applied


Step 3 Set-up Camera, lens and illumination

Check camera lens

– fully open at night & set correctly

Check model number to Raytec performance specification to ensure required distance is

achievable;

- Check illuminator is set to max power
- Check orientation of illuminator and ensure it is pointing in correct direction
- Check angle of illuminator (Holographic lens) – Too narrow may cause hot spots

and the aperture of the camera lens to close down. Too wide and there may be
insufficient light on scene and light going where it is not needed.