Dr10-95, Dry coolers, Mechanical data- condensers and dry coolers – Airedale Dry coolers DR10 User Manual
Page 21

DR10-95
DRY COOLERS
Dry coolers
21
Technical Manual :6877401 V1.1.0 02_2013
Mechanical Data- Condensers and Dry Coolers
DR40
DR50
DR55
Total Heat of Rejection DR
(1)
kW
41.8
53
54.4
Dimensions - Horizontal
(2)
H x W x L
mm
1167 x 1000 x 3565
1167 x 1000 x 3565
1167 x 1000 x 3565
Dimensions - Vertical
(2)
H x W x L
mm
1090 x 1167 x 3565
1155 x 1167 x 3565
1090 x 1167 x 3565
Weight
Machine
kg
208
258
260
Construction
Material/Colour
Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)
Dry Cooler
Air Cooled - Copper Tube/Turbulated Aluminium Fins
Total Face Area
m²
3.63
3.63
3.63
Nominal Airflow
m³/s
7.5
10.8
6.6
Discharge
-H Horizontal or -V Vertical (Please Specify at Order)
Fan & Motor
Axial
Quantity
3
3
3
Diameter
mm
630
710
630
Maximum Speed
rpm
895
930
895
Dry Cooler
Internal Water Volume
L
23.1
23.1
43.2
Water flowrate
l/s
2.0
2.5
2.6
Pressure Drop
kPa
48.5
70
32
OPTIONAL EXTRAS
Short Case Axial Fan
Designed to 75 Pa ESP
Dimensions - Horizontal
H x W x L
mm
1167 x 1000 x 3565
1167 x 1000 x 3565
1167 x 1000 x 3565
Dimensions - Vertical
H x W x L
mm
1130 x 1167 x 3565
1140 x 1167 x 3565
1130 x 1167 x 3565
Weight
Machine
kg
242
249
294
EC Fan
Dimensions - Horizontal
H x W x L
mm
1167 x 1000 x 3565
1167 x 1000 x 3565
1167 x 1000 x 3565
Dimensions - Vertical
H x W x L
mm
1127 x 1167 x 3565
1170 x 1167 x 3565
1127 x 1167 x 3565
Weight
Machine
kg
228
293
280
(1) Nominal data based on 35°C ambient and a 45/40°C Water entering / leaving.
(2) Overall dimensions for clearance; refer to
Dimensional & Installation Data
, for detail.