Mechanical data, Condensers and dry coolers, Dr10-95 – Airedale Dry coolers DR10 User Manual
Page 19: Dry coolers, Mechanical data – condensers and dry coolers

DR10-95
DRY COOLERS
Dry coolers
19
Technical Manual :6877401 V1.1.0 02_2013
Mechanical Data
– Condensers and Dry Coolers
DR10
DR12
DR15
Total Heat of Rejection DR
(1)
kW
11.1
13.7
15.3
Dimensions - Horizontal
(2)
H x W x L
mm
1167 x 1000 x 1102
1167 x 1000 x 1102
1167 x 1000 x 1102
Dimensions
– Vertical
(2)
H x W x L
mm
1090 x 1167 x 1102
1155 x 1000 x 1102
1090 x 1167 x 1102
Weight
Machine
kg
77
93
90
Construction
Material/Colour
Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)
Dry Cooler
Air Cooled - Copper Tube/Turbulated Aluminium Fins
Total Face Area
m²
0.91
0.91
0.91
Nominal Airflow
m³/s
2.3
3.3
1.9
Discharge
-H Horizontal or -V Vertical (Please Specify at Order)
Fan & Motor
Axial
Quantity
1
1
1
Diameter
mm
630
710
630
Maximum Speed
rpm
895
930
895
Dry Cooler
Internal Water Volume
L
6.6
6.6
11.9
Nominal Flowrate
l/s
0.53
0.65
0.7
Pressure Drop
kPa
11.9
17.8
20.7
OPTIONAL EXTRAS
Short Case Axial Fan
Designed to 75 Pa ESP
Dimensions - Horizontal
H x W x L
mm
1167 x 1000 x 1102
1167 x 1000 x 1102
1167 x 1000 x 1102
Dimensions - Vertical
H x W x L
mm
1130 x 1167 x 1102
1140 x 1167 x 1102
1130 x 1167 x 1102
Weight
Machine
kg
88
105
101
EC Fan
Dimensions - Horizontal
H x W x L
mm
1167 x 1000 x 1102
1167 x 1000 x 1102
1167 x 1000 x 1102
Dimensions - Vertical
H x W x L
mm
1127 x 1167 x 1102
1170 x 1167 x 1102
1127 x 1167 x 1102
Weight
Machine
kg
83
90
96
(1)
Nominal data based on 35°C ambient and 45/40°C Water entering / leaving.
(2)
Overall dimensions for clearance;.