beautypg.com

Performance data, Capacity data - cooling only unit, Operating limits – Airedale StoreMaster 50kW - 77kW User Manual

Page 29: Comfort storemaster, Comfort range, Dx (mechanical) cooling only, Free cooling only

background image

Comfort

STOREMASTER

Comfort Range

29

Technical Manual : 6678403 V1.3.0_ 02_2013

Performance Data

CAPACITY DATA - COOLING ONLY UNIT

DX (Mechanical) Cooling Only

Ambient

20°C

25°C

30°C

35°C

40°C

Air On

°C DB / %RH

TC

kW

SC

kW

EER

TC

kW

SC

kW

EER

TC

kW

SC

kW

EER

TC

kW

SC

kW

EER

TC

kW

SC

kW

EER

STM50R-P

20 / 50

54.3

51.6

3.9

52.5

49.9

3.5

50.4

48.1

3.1

48.2

46.1

2.8

45.9

44.0

2.4

22 / 50

56.9

52.0

4.1

55.0

50.4

3.7

52.8

48.7

3.3

50.5

46.8

2.9

48.1

44.7

2.5

24 / 50

59.5

52.1

4.2

57.5

50.6

3.8

55.3

49.0

3.4

53.0

47.2

3.0

50.5

45.3

2.6

26 / 50

62.3

51.9

4.4

60.3

50.4

3.9

58.1

48.9

3.5

55.7

47.2

3.1

53.0

45.3

2.7

STM77R-P

20 / 50

80.2

77.1

3.7

77.4

74.5

3.3

74.1

71.6

3.0

70.6

68.4

2.6

66.6

64.8

2.2

22 / 50

83.8

78.1

3.9

80.8

75.6

3.5

77.4

72.9

3.1

73.7

69.8

2.7

69.7

66.4

2.3

24 / 50

87.9

79.0

4.0

84.8

76.7

3.6

81.3

74.0

3.2

77.5

71.1

2.8

73.2

67.8

2.4

26 / 50

92.1

79.2

4.2

88.8

77.0

3.7

85.2

74.5

3.3

81.1

71.7

2.9

76.5

68.6

2.5

TC = Total Cooling SC = Sensible Cooling EER = Energy Efficiency Ratio

(1)

Figures are Gross.

(2)

Energy Efficiency Ratio (EER) is Total Cooling duty ÷ Unit Input Power, where input power includes compressor, supply fan and condenser fan.

Free Cooling Only

Ambient

10°C

15°C

20°C

25°C

Air On

°C DB / %RH

TC kW

EER

TC kW

EER

TC kW

EER

TC kW

EER

STM50R-P

20 / 50

36.7

19.3

18.4

9.7

-

-

-

-

22 / 50

44.1

23.2

25.7

13.5

7.3

3.9

-

-

24 / 50

51.4

27.1

33.0

17.4

14.7

7.7

-

-

26 / 50

58.8

30.9

40.4

21.3

22.0

11.6

3.7

1.9

STM77R-P

20 / 50

67.3

18.7

33.7

9.4

-

-

-

-

22 / 50

80.8

22.4

47.1

13.1

13.5

3.7

-

-

24 / 50

94.2

26.2

60.6

16.8

26.9

7.5

-

-

26 / 50

107.7

29.9

74.1

20.6

40.4

11.2

6.7

1.9

TC = Total Cooling SC = Sensible Cooling EER = Energy Efficiency Ratio

(1)

Figures are Gross. i.e. Q = m Cp

ΔT

(2)

Energy Efficiency Ratio (EER) is Total Cooling duty ÷ Unit Input Power, where input power includes compressor and supply fan.

OPERATING LIMITS

Unit with Electronic Fan Speed HP Control (-20°C)

Minimum Ambient Air DB°C

-20°C

Maximum Ambient Air DB°C

+40°C

For applications outside of these conditions, please refer to Airedale.