Rola-Chem Digital Controller PN 554237 02/17/2014 Page: 7 of 12


Note: Turning the controller “OFF” using the MODE button simply turns off the
controller functions, but does not turn off the power to the controller. The FLOW lamp
is both the power light and a flow indicator when flow switch is used.

• When Flow light is on and Auto light is off, levels can be set.

Set level button: Pressing the set level button once will display the current set level. To

change the set level, press the set level button until the desired level is reached.


Feed time: The feed times are displayed in seconds.

Each feed cycle includes a five (5) minute delay time. Pressing the feed time
button allows the user to select available feed times. Release the button when the
desired ORP feed time is reached. To set the controller in constant feed, release
the button when the display reads “con”.

AUTO mode: This is normal operation mode. The controller operates the feeder

to automatically maintain the parameters set for ORP.

4.0 Installation

4.1 Locating the controller

Install the chemical pump/ feed systems as shown in manuals included with the
feeders. Before installing the controller, it is important to do a site assessment to
consider where and how you will mount the unit. The controller should be mounted
on a wall or other surface within eight feet of the feeder, at least ten feet away from
the edge of the water, and within six feet of the GFCI power

source. Never mount a

controller above or near an acid tank. Never mount a controller in a location
accessible to the public. See appendix for typical feed system schematics.

4.2 Mechanical Installation

Once the site is selected, obtain screws or anchors

to securely mount the controller

on the wall or a panel.


Screw slots are provided in the controller enclosure. Access to flow switch wires,
acid/base changes and terminals is located on the back of the enclosure.