0 appendix 7.1 dip switch settings – Rola-Chem 554300 Dual ORP/pH Digital Controller User Manual
Page 16

7.0 Appendix
7.1 Dip switch settings
The controller has dip switches to control functions/options that are not accessible on the front panel.
These dip switches are located inside the power access panel. See section 3.3.
It is recommended that switches #1 and #2 be in the ON position.
Control Switch Description
ORP/pH interlock
#1
OFF
ORP chemical feeding is independent of pH feeding and range.
#1 ON
ORP chemical feed only when pH is within limits.
ORP will not feed when pH chemical is feeding.
Feed mode limit -Timed feed Mode (Time set on front panel)
#2
OFF
There is no consecutive feed limit.
#2 ON
The pH & ORP chemical feeder outputs go through a preset number of
consecutive feed cycles before feeders are disabled. If preset count is
reached for either pH or ORP, the respective feeder outputs will be
disabled and its display will flash.
The number of consecutive feed cycles is 3 to 20 (default is 10) and
can be independently set for both pH and ORP.
To adjust the time out feature in the 'timed feed mode'
1) Turn off & remove power, then move #2 dip switch to ON.
2) Re-power & press MODE to set it for ORP or pH
3) Set FEED TIME to OFF
4) Press FEED ONCE to select the feed count
5) Press FEEDTIME and return the time to the desired cycle
Feed mode limit -Continuous feed Mode (Time set to 'con' on front panel)
#2
OFF
There is no consecutive feed limit.
#2 ON
The pH & ORP chemical feeder outputs continuously feed for a preset
time before feeders are disabled. If the preset time period is reached
for either pH or ORP, the respective feeder output will be disabled
and it's display will flash.
The time out period can be set from 10 to 99 minutes (default is 10
minutes) and can be independently set for both pH and ORP.
To adjust the time out feature in the 'continuous feed mode'
1) Turn off & remove power, then move #2 dip switch to ON
2) Re-power & press MODE to set it for ORP or pH
3) Set FEED TIME to ‘con’
4) Press FEED ONCE button to select the default feed time
Acid/Base pH chemical feed
#3
OFF
Unit set to feed acid chemical when pH is over set-point
#3 ON
Unit set to feed base chemical when pH is under set-point
Keypad Lockout
#4
OFF
Key pad operable to set controller parameters
#4 ON
Key pad operable only for pH calibration. Other parameters stay at
settings established prior to moving dip switch #4
Rola-Chem Digital Controller PN 554331 6/01/2012 Page: 16 of 20