beautypg.com

Pyromation Series 810 1_8 DIN User Manual

Page 2

background image

Parameter

Legend

for 1 sec

followed

by

Set

Value

Adjustment Range &

Description

Default

Value

Units

Display

(

1

/

8

Din

Only )

Ww

Ww

Ww

Ww

Read/Write

Comms Write

Read only

Ww

Ww

Ww

Ww

Reset latched relay(s)

Initiate Tare (zero display)
Reset min/max PV values

Reset Alarm 1 elapsed time

Digital Input

Usage

Reset Alarm 1 elapsed time

& min/max PV values

Config Lock

####

Config Mode lock code, to

))))

))))

))))

))))

4. SETUP MODE

Note: Configuration must be completed before adjusting Setup parameters.

First select Setup mode from Select mode (refer to section 2). Press to scroll

through the parameters

(while this key is pressed, and for 1 sec after, the parameter

legend is shown, then the current value)

. Press or to change the value.

To exit from Setup mode, hold down and press to return to Select mode.

Note: Parameters displayed depends on how instrument has been configured.

Parameter

Legend

for 1 sec

followed

by

Set

Value

Adjustment Range &

Description

Default

Value

Units

Display

(

1

/

8

Din

Only )

Input Filter Time

Constant

OFF or 0.5 to 100.0 secs

.

Process Variable

Offset

±

Span of controller

.

Raw PV value

Linear input value, un-scaled (mA, mV or VDC)

blank

High Alarm 1

Max

Low Alarm 1

Alarm 1 value, adjustable within scaled

range, in display units

Min

(

Alm1

only = )

Alarm 1

Hysteresis

1 LSD to full span in display units on

safe side of alarm

High Alarm 2

Max

Low Alarm 2

Min

Al 2 Hysteresis

Options as for alarm 1

!!!!

High Alarm 3

Max

Low Alarm 3

Min

Al 3 Hysteresis

Options as for alarm 1

*

*

*

*

High Alarm 4

Max

Low Alarm 4

Min

Al 4 Hysteresis

Options as for alarm 1

High Alarm 5

Max

Low Alarm 5

Min

Al 5 Hysteresis

Options as for alarm 1

5

5

5

5

Scaling

Breakpoint 1

####

Multi-point scaling breakpoint 1 value,
adjustable from to

in % of span

Display Value 1

Value to be displayed at multi-point

scaling breakpoint 1, in display units

Range

Max

Scaling

Breakpoint 2

####

Multi-point scaling breakpoint 2, adjustable up to

100% of span. Must be >

####

value

Display Value 2

Value to be displayed at Multi-point scaling

breakpoint 2, in display units

Scaling

Breakpoint 3

####

Multi-point scaling breakpoint 3, adjustable up to

100% of span. Must be >

####

value

Display Value 3

Value to be displayed at Multi-point scaling

breakpoint 3, in display units

Scaling

Breakpoint 4

####

Multi-point scaling breakpoint 4, adjustable up to

100% of span. Must be >

####

value

Display Value 4

Value to be displayed at Multi-point scaling

breakpoint 4, in display units

Scaling

Breakpoint 5

####

Multi-point scaling breakpoint 5, adjustable up to

100% of span. Must be >

####

value

Display Value 5

Value to be displayed at Multi-point scaling

breakpoint 5, in display units

Scaling

Breakpoint 6

# %

# %

# %

# %

Multi-point scaling breakpoint 6, adjustable up to

100% of span. Must be >

####

value

Display Value 6

%%%%

Value to be displayed at Multi-point scaling

breakpoint 6, in display units

%%%%

Scaling

Breakpoint 7

# *

# *

# *

# *

Multi-point scaling breakpoint 7, adjustable up to

100% of span. Must be >

# %

# %

# %

# %

value

Display Value 7

*

**

*

Value to be displayed at Multi-point scaling

breakpoint 7, in display units

*

**

*

Scaling

Breakpoint 8

# (

# (

# (

# (

Multi-point scaling breakpoint 8, adjustable up to

100% of span. Must be >

# *

# *

# *

# *

value

Display Value 8

(

((

(

Value to be displayed at Multi-point scaling

breakpoint 8, in display units

(

((

(

Scaling

Breakpoint 9

#### )

))

)

Multi-point scaling breakpoint 9, adjustable up to

100% of span. Must be >

# (

# (

# (

# (

value

Display Value 9

)

))

)

Value to be displayed at Multi-point scaling

breakpoint 9, in display units

)

))

)

Tare Feature

Enables or disables the input

auto-zero Tare feature

Setup Lock Code

####

to

))))

))))

))))

))))

Note: Operator mode screens follow, without exiting from Setup mode.

5. MESSAGES & ERROR INDICATIONS

These messages indicate that the instrument may require attention, or there is a

problem with the signal input connection.

The message legend is shown for 1

second, followed by its value.

Caution:

Do not continue with the process until the issue is resolved.

Parameter

Legend

for 1 sec

followed

by

Value Description

Units

Display

(

1

/

8

Din

Only )

Instrument

parameters are in

default conditions

Configuration & Setup is required.

This screen is seen at first turn on,

or if hardware configuration is

changed. Press to enter

Configuration Mode, next press

or to enter the unlock code,

then press to proceed

Input Over Range

++++

,

,,

,

Input signal is > 5% over-range

Input Under Range

++++ ,

,,

,

Input signal is > 5% under-range

(>10% under-range for 4 to 20mA,

1 to 5V and 2 to 10V

ranges)

Input Sensor Break

-

-

-

-

Break detected in input signal

sensor or wiring

Option 1 Error

..

..

..

..

Option 1 module fault

Option 2 Error

..

..

..

..

Option 2 module fault

Option 3 Error

..

..

..

..

Option 3 module fault

Option A Error

..

..

..

..

Option A module fault

Option B Error

..

..

..

..

..

..

..

..

Shown if any module is fitted

(option B not used on Indicators)

Note:

++++

,

,,

,

,

++++ ,

,,

,

or

-

-

-

-

may also be displayed if an incorrect input type is

selected.

6. OPERATOR MODE

This mode is entered at power on, or accessed from Select mode (see section 2).

Note: All Configuration mode and Setup mode parameters must be set as

required before starting normal operations.

Press to scroll through the parameters

(while this key is pressed, and for 1 sec

after, the parameter legend is shown, followed by the current value)

.

Note: All Operator Mode parameters in Display strategy 6 are read only (see

in configuration mode), they can only be adjusted via Setup mode.

Legend

for 1 sec

followed

by

Value Display Strategy and

When Visible

Description

Units

Display

(

1

/

8

Din

Only )

####

PV

Value*

Always

Process Variable value

Read only

Latched outputs can be reset

°

,

°

or

blank

Mm

Mm

Mm

Mm

Max PV

Value Strategies , , , , &

%%%%

Maximum displayed value

(inc

++++

,

,,

,

or

-

-

-

-

)

since

Mm

Mm

Mm

Mm

last reset.

To reset, press or for

3 seconds,

display =

&&&&

when reset

°

,

°

or

blank

Mm

Mm

Mm

Mm

Min PV

Value Strategies , , , , &

%%%%

Minimum displayed value

(inc

++++ ,

,,

,

or

-

-

-

-

)

since

Mm

Mm

Mm

Mm

last reset.

To reset, press or for

3 seconds,

display =

&&&&

when reset

°

,

°

or

blank

Elapsed

Time

Strategies , &

%%%%

if alarm 1 configured.

Format mm.ss to 99.59

then mmm.s

(10 sec increments)

Shows

++++

,

,,

,

if >999.9

Accumulated alarm 1 active

time since

last reset.

To reset, press or for

3 seconds,

display =

&&&&

when reset

Alarm 1

Value

Strategies , , &

%%%%

if alarm 1 configured

Alarm 1 value, adjustable

except in Strategy 6

(

Alm1

only = )

Alarm 2

Value

Strategies , , &

%%%%

if alarm 2 configured

Alarm 2 value, adjustable

except in Strategy 6

Alarm 3

Value

Strategies , , &

%%%%

if alarm 3 configured

Alarm 3 value, adjustable

except in Strategy 6

Alarm 4

Value

Strategies , , &

%%%%

if alarm 4 configured

Alarm 4 value, adjustable

except in Strategy 6

Alarm 5

Value

Strategies , , &

%%%%

if alarm 5 configured

Alarm 5 value, adjustable

except in Strategy 6

Active

Alarm

Status*

When one or more

alarms are active

L

Alarm 4 active

Alarm 2 active

Alarm 3 active
Alarm 5 active

Latched outputs can be reset

if

alarm 1

active

Alarm Indication

The Active Alarm Status screen indicates any active alarms. In addition, the

associated Alarm LED flashes.

For latching alarm outputs, the LED flashes when the alarm condition exists,

and goes to ON when the alarm condition is no longer present if the output has not

yet been reset.

*Resetting Latched Alarm Outputs

Any latched outputs can be reset whilst the Process variable or Alarm Status

screens are displayed, by pressing the or key, via the Digital Input (if fitted)

or with a communications command via the RS485 module (if fitted).

Note: Outputs will only reset if their alarm condition is no longer present.

Caution:

A reset will affect ALL latched outputs.

Additional

1

/

8

Din Indicator Units Display and LED’s

In Operator Mode, a Units display shows

°

or

°

when temperature values are

shown. This display is also used in other modes as a confirmation of the parameter

type currently shown in the main display. The SET LED indicator is off in

Operator Mode, Flashing in Configuration Mode and ON in Set-up mode.

MIN and MAX LED’s light when these stored values are shown.

Multi-Point Scaling

When enabled (

Mm

Mm

Mm

Mm

=

),

up to 9 breakpoints can be set to

compensate for non-linear input

signals.

For each breakpoint, the input
scale value (

####

n) is entered

in % of input span, followed by
the value to be shown (

n)

in display units.

Each breakpoint’s input scale

value must be higher than the

previous value, but the display

values can be higher or lower.

Any scale value set to 100%

becomes the last in the series.

Tare Feature

When Tare is enabled (

=

), it can be used to set the displayed value to

zero automatically, by making the PV Offset parameter equal, but opposite to, the

current process variable value. Tare can be initiated via the Digital Input (if fitted),

with a communications command via the RS485 module (if fitted) or by using the

following key press sequence:

Press until the process variable is displayed.
Hold down and together for three seconds until the display shows

/ $

/ $

/ $

/ $????

Release both keys and press within 3 seconds to confirm the request.
The display should read briefly, then begin responding to input signal changes.

Note: Tare request is aborted if this sequence is not followed exactly.

7. PRODUCT INFORMATION MODE

First select Product information mode from Select mode (refer to section 2).

Press to view each parameter

(while this key is pressed, and for 1 sec after, the

parameter legend is shown, followed by its value)

. Hold down and press to

return to Select mode. Note: These parameters are all read only.

Parameter

Legend

for 1 sec

followed

by

Value Description

Units

Display

(

1

/

8

Din

Only )

Input type

'

'

'

'

Universal input
No option fitted

/

/

/

/

Relay output
SSR drive output
Triac output

Option 1 module

type fitted

Linear DC voltage / current output
No option fitted

/

/

/

/

Relay output

/

/

/

/

Dual Relay (outputs 2 & 4)
SSR drive output
Triac output

Option 2 module

type fitted

Linear DC voltage / current output
No option fitted

/

/

/

/

Relay output

/

/

/

/

Dual Relay (outputs 3 & 5)
SSR drive output
Linear DC voltage / current output

Option 3 module

type fitted

####

24V DC Transmitter power supply
No option fitted

(

((

(

RS485 communications

Auxiliary Option A

module type fitted

Digital Input

Firmware type

01

01

01

01

Value displayed is firmware type number

Firmware issue

'$$

'$$

'$$

'$$

Value displayed is firmware issue number

Product Rev Level

.

.

.

.

Value displayed is Product Revision Level

Manufactured Date

Mm

Mm

Mm

Mm

Month & year of manufacture. Format mmyy

Serial number 1

First four digits of serial number

Serial number 2

Middle four digits of serial number

Serial number 3

Last four digits of serial number

####

8. SERIAL COMMUNICATIONS

Refer to the full user guide (available from your supplier) for details.

9. SPECIFICATIONS

UNIVERSAL INPUT

Thermocouple

Calibration:

±

0.1% of full range,

±

1LSD (

±

1°C for Thermocouple CJC).

BS4937, NBS125 & IEC584.

PT100 Calibration:

±

0.1% of full range,

±

1LSD.

BS1904 & DIN43760 (0.00385

/

/°C).

DC Calibration:

±

0.1% of full range,

±

1LSD.

Sampling Rate:

4 per second.

Impedance:

>10M

resistive, except DC mA (5

) and V (47k

).

Sensor Break

Detection:

Thermocouple, RTD, 4 to 20 mA, 2 to 10V and 1 to 5V ranges

only. High alarms activate for thermocouple/RTD sensor break,

low alarms activate for mA/V DC sensor break.

Isolation:

Isolated from all outputs (except SSR driver).

Universal input must not be connected to operator accessible

circuits if single relay outputs are connected to a hazardous

voltage source. Supplementary insulation or input grounding

would then be required.

DIGITAL INPUT

Voltage Input:

Volt-free Contacts:

Reset or Tare occurs on high (2 to 24VDC) to low <0.8VDC, or

Open to Closed transition.

Isolation:

Reinforced safety isolation from inputs and other outputs.

OUTPUTS

Relay

Contact Type &

Rating:

Single pole double throw (SPDT), latching or non-latching

action (selectable); 2A resistive at 120/240VAC.

Lifetime:

>500,000 operations at rated voltage/current.

Isolation:

Basic Isolation from universal input and SSR outputs.

Dual Relay

Contact Type &

Rating:

Single pole single throw (SPST), latching or non-latching

action (selectable); 2A resistive at 120/240VAC.

Lifetime:

>200,000 operations at rated voltage/current.

Isolation:

Reinforced safety isolation from inputs and other outputs.

SSR Driver

Drive Capability:

SSR drive voltage >10V into 500

min.

Isolation:

Not isolated from universal input or other SSR driver outputs.

Triac

Operating Voltage: 20 to 280Vrms (47 to 63Hz).
Current Rating:

0.01 to 1A (full cycle rms on-state @ 25°C);

derates linearly above 40°C to 0.5A @ 80°C.

Isolation:

Reinforced safety isolation from inputs and other outputs.

Linear DC

Accuracy:

±

0.25% (mA @ 250 , V @ 2k ). Degrades linearly to

±

0.5%

for increasing burden (to specification limits).

Resolution:

8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical).

Isolation:

Reinforced safety isolation from inputs and other outputs.

Transmitter PSU

Power Rating:

24V TxPSU Module; Unregulated 20 to 28V DC into 910

min

Linear output Module; Regulated 0.0 to 10.0V into 500

min.

Isolation:

Reinforced safety isolation from inputs and other outputs.

SERIAL COMMUNICATIONS

Physical:

RS485, at 1200, 2400, 4800, 9600 or 19200 bps.

Protocols:

Selectable between Modbus and West ASCII.

Isolation:

Reinforced safety isolation from all inputs and outputs.

OPERATING CONDITIONS (FOR INDOOR USE)

Ambient

Temperature:

0°C to 55°C (Operating), –20°C to 80°C (Storage).

Relative Humidity: 20% to 95% non-condensing.
Supply Voltage and

Power:

100 to 240VAC

±

10%, 50/60Hz, 7.5VA

(for mains powered versions), or

20 to 48VAC 50/60Hz 7.5VA or 22 to 65VDC 5W

(for low voltage versions).

ENVIRONMENTAL

Standards:

CE, UL & ULC

EMI:

Complies with EN61326 (Susceptibility & Emissions).

Safety

Considerations:

Complies with EN61010-1 & UL3121.

Pollution Degree 2, Installation Category II.

Front Panel Sealing: To IP66 (IP20 behind the panel).

PHYSICAL

Front Bezel Size:

1

/

16

Din = 48 x 48mm,

1

/

8

Din = 96 x 48mm

Depth Behind Panel:

1

/

16

Din = 110mm,

1

/

8

Din = 100mm.

Weight:

0.21kg maximum.

PV Input Signal

% of Span

D

is

pl

ay

ed

V

al

ue