beautypg.com

Dimensions and specifications, Specifications – Precision Control Systems 930 User Manual

Page 24

background image

Model 930 ControlIR

TM

Instruction Manual

Dimensions and Specifications

Research, Inc.

Page 20 of 25







SPECIFICATIONS

Dimensions and
Specifications



Environmental Limits:

Operating Temperature

0-50 deg. C (32-122 deg. F)

Storage Temperature

-40-70 deg. C (-10-158 deg. F)

Humidity

0-90 %, non-condensing

Clearance

4” (100mm) on right and left sides


Weight:

The system weight varies slightly with the options installed. The maximum weight of
the system is ??? pounds (??? kg).

Operating Voltage:

240 or 480-VAC +10%, -15% at 50 or 60 Hertz. Voltage set at factory per order.

Operating Current and kW:

Current Rating of System

Continuous Current

Rating at 50

°C

Maximum Power kW at

240 VAC

480 VAC

120 Amp

120 Amps

50

99.8

160 Amp

160 Amps

66.5

133


Line Fusing:

Current Rating of System

Fuse Type

Fuse Rating

120 Amp

JJS-150

Class T 150 Amp 600 Volt

160 Amp

JJS-200

Class T 200 Amp 600 Volt


Power Control:

Control Mode:

SCR phase-angle control of the voltage applied to a three phase load. True RMS
voltage feedback for load voltage regulation.

Control Range:

0-98% of supply voltage.

Output Linearity:

RMS load voltage varies linearly with control signal, within +/- 2 percent of span
over the entire range of control.