beautypg.com

7202installop, Tork, Installation and operating instructions – NSi Industries 7100 User Manual

Page 5

background image

TORK MODEL 7202

24 HR. TIME SWITCH

WITH SKIP-A-DAY

SWITCH: DPST
CONTACT RATINGS:

40 AMP 120-277VAC
40 AMP TUNGSTEN 120VAC
20 AMP INDUCTIVE

120-277VAC SINGLE PHASE

1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC

TIMING MOTOR:
208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.

INSTALLATION AND OPERATING INSTRUCTIONS

TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on
dial edge as shown in figure and set point of each tripper to
desired operating time. CAUTION: Note if selected time is AM
or PM. Hold tripper against dial edge and firmly tighten
knurled screw.

TO SET DIAL TO TIME: Turn dial counter-clockwise until correct time is indicated by arrow on name-
plate.

FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever
on left of nameplate to turn OFF.

TO OMIT ON OPERATION: 7 spoke wheel at lower left of 24 hour dial moves ahead once each day,
about 5 hours before the first ON tripper is set to operate. Insert brass knurled screws in appropriate
spokes on days when ON operations are to be omitted.

TO SET OMITTING WHEEL TO CORRECT DAY: Hold down OFF lever on left of
nameplate. The red stud on this lever is the day-indicator. If the ON tripper has
already passed the omitting wheel, turn omitting wheel clockwise until the present
day of the week is indicated. If ON tripper has not passed omitting wheel, set omit-
ting wheel so preceding day is indicated (24 hour dial turns counter-clockwise).

TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and
swing the movement out. To replace, insert main-plate projections in slots opposite latch and swing
movement in until it latches.

Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)

O
F
F

O
N

TORK

Dial Calibrations

Knurled Screw

OFF TIME

(Dark Tripper)

ON TIME

(Light Tripper)

MANUAL

ON

LEVER

MANUAL

OFF

LEVER

TIME

TORK

®

1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542

FAX: 914-664-5052

LI-590(A)

RED

STUD

GREEN

ACTUATOR

H

M

L

1

X

2

H

LOAD

LOAD

LOAD

208-240V

SUPPLY

277V

SUPPLY

H

M

L

1

X

2

N

H

MUST BE

SAME PHASE