KYORITSU 8130 User Manual

Kew 8130, Power clamp sensor series, Flexible clamp sensor

background image

3. CLAMP SENSOR LAYOUT

4. PIN ASSIGNMENT FOR OUTPUT TERMINAL

The pin assignment for the output terminal of this clamp sensor is as

follows.

* Pin assignment at the connecting terminal of measuring instrument

is symmetrical to above figure.

Output signal passes between 3 and 5 of Output terminal.

This clamp sensor is supplied power via an Output cable. Power

supply of +3.0 to +5.5V is required between 1 and 3 of Output

terminal and -3.0 to -5.5V is required between 2 and 3 of Output

terminal.

#

WARNING

Never attempt to make any measurement if any abnormal

conditions, such as a broken cover or exposed metal parts are

present on the clamp sensor.

Do not disassemble, install substitute parts or make any

modification to the clamp sensor. Return the clamp sensor to

your local KYORITSU distributor for repair or re-calibration in

case of suspected faulty operation.

Do not use the clamp sensor if the clamp sensor or your hands

are wet. Otherwise, electrical shock accident may occur.

Use insulated protective gears for your safety when using this

clamp sensor.

#

CAUTION

Do not step on or pinch the cord; it may damage the jacket of cord.

Do not expose the clamp sensor to direct sunlight, high temperatures,

humidity or dew. Otherwise, it may cause deformation or insulation

degradation and cannot meet the original specification.

Not to give shocks, such as vibration or drop, which may

damage the clamp sensor, during transit or use.

Use a damp cloth with water or neutral detergent for cleaning the

clamp sensor. Do not use abrasives or solvents.

This clamp sensor is not designed to be dust or waterproof. Do

not use it dusty places or where the clamp sensor is likely to be

wet. It may cause troubles on the clamp sensor.

Never pinch foreign matters or give vibrations at the jointed

parts of this clamp sensor. Otherwise, matching area of Jaws

may be damaged and cause influences on the measurements.

Do not bend or pull the root of the cable in order to prevent

breaks in the cable.

Never apply the current exceeding the measuring range for a

long time. It may damage the clamp sensor.

Never connect/remove the connectors while connected devices

are on or clamping onto the conductor under test. Otherwise, the

connected devices or clamp sensors may be damaged.

Accurate measurement may not be obtained in the vicinity of

strong magnetic fields such as transformers, high-current

circuits or wireless machines.

Meaning of symbols on the clamp sensor:

#

User must refer to the explanations in the instruction manual

for safety reasons.

Clamp sensor with double or reinforced insulation
Do not apply around or remove from un-insulated hazardous

live conductors, which may render electric shock, electric

burn, or arc flash.

AC
Crossed-out wheel bin symbol (according to WEEE Directive:

2002/ 96/ EC) indicating that this electrical product may not

be treated as household waste, but that it must be collected

and treated separately.

Cautions for using this clamp sensor with KEW5010/5020:

Some KEW5010/5020 that were manufactured before the specific

timing of production may not be used with this clamp sensor. Please

refer to “

6-3 Connecting with Logger (KEW5010/5020)” and

check the serial no..

1. SAFETY WARNINGS

This clamp sensor has been designed and tested according to

IEC61010-1: Safety Requirements for Electronic Measuring Apparatus,

and delivered in the best condition after passing quality control tests.

This instruction manual contains warnings and safety rules which have

to be observed by the user to ensure safe operation of the clamp

sensor and to maintain it in safe condition. Therefore, read through

these operating instructions before using the clamp sensor.

#

DANGER

Read through and understand instructions contained in this

manual before starting to use the clamp sensor.

Keep the manual at hand to enable quick reference whenever

necessary.

The clamp sensor is to be used only in its intended applications.

Understand and follow all the safety instructions contained in

the manual.

It is essential that the above instructions are adhered to. Failure to

follow the above instructions may cause injury, clamp sensor

damage and/or damage to equipment under test. KYORITSU is not

liable for any damage resulting from the user’s mishandling of the

clamp sensor.

The symbol # indicated on the clamp sensor means that the user

must refer to the related parts in the manual for safe operation of the

clamp sensor. It is essential to read the instructions wherever the #

symbol appears in the manual.

#

DANGER: is reserved for conditions and actions that are likely

to cause serious or fatal injury.

#

WARNING: is reserved for conditions and actions that can

cause serious or fatal injury.

#

CAUTION: is reserved for conditions and actions that can

cause injury or instrument damage.

#

DANGER

With attention to the measurement category to which the object

under test belongs, and do not make measurements on a circuit

in which the electrical potential exceeds the following values:

300V for CAT. IV and 600V for CAT. III or lower categories.

Measurement Category:

To ensure safe operation of measuring instruments, IEC 61010

establishes safety standards for various electrical environments,

categorized as O to CAT.IV, and called measurement categories.

Higher-numbered categories correspond to electrical environments

with greater momentary energy, so a measuring instrument designed

for CAT.III environments can endure greater momentary energy than

one designed for CAT.II.

O

: Circuits which are not directly connected to the mains

power supply.

CAT.II : Electrical circuits of equipment connected to an AC

electrical outlet by a power cord.

CAT.III : Primary electrical circuits of the equipment connected

directly to the distribution panel, and feeders from the

distribution panel to outlets.

CAT.IV : The circuit from the service drop to the service entrance,

and to the power meter and primary over-current

protection device (distribution panel).

2. FEATURES

This is a Clamp Sensor capable of measuring AC current up to

1000A.

Flexible and light weight because of an air core coil used at the

Clamp Sensor part

5. SPECIFICATION

Model name

KEW8130

Rated current

AC1000A

Output voltage

AC500mV/AC1000A(0.5mV/A)

Measuring range

AC0 - 1000Arms(1850Apeak)

Accuracy

(sine wave input)

±0.8%rdg±0.2mV(45 - 65Hz)

±1.5%rdg±0.4mV(40 - 1kHz)

Phase characteristics

45 to 65Hz: within ±2°

40 to 1kHz: within ±3°

Current consumption

(at power supply ±5V)

max. 2mA

Temperature & humidity

range (guaranteed accuracy)

23±5ºC, Relative humidity: 85% or

less (no condensation)

Operating temperature &

humidity range

-10 to 50ºC, Relative humidity: 85% or

less (no condensation)

Storage temperature &

humidity range

-20 to 60ºC, Relative humidity: 85% or

less (no condensation)

Max allowable input

AC1300A (continuous)

Output impedance

100Ω or less

Environmental condition

Altitude up to 2000m, in-door use

Applicable standards

IEC 61010-1

IEC 61010-2-030

IEC 61010-2-032

Measurement CAT III(600Vrms), CAT

IV (300Vrms)

Pollution degree 2

IEC 61326-1

Withstand voltage

AC5160V (r.m.s. 50/60Hz) / 5 sec.

Between circuit – clamp sensor

Insulation resistance

50MΩ or more/ 1000V

Between circuit – clamp sensor

Measureable conductor size Max ø 110mm
Cable length

Between clamp sensor – circuit box:

approx. 2.7m

Between circuit box – output terminal:

approx. 0.2m

Output terminal

MINI DIN 6PIN

Weight

Approx. 180g

Accessories

Instruction manual

Cable marker: No.1 to 3 (2pcs each)

Carrying case (MODEL9095)

6. OPERATING INSTRUCTIONS

#

DANGER

With attention to the measurement category to which the object

under test belongs, and do not make measurements on a circuit

in which the electrical potential exceeds the following values:

300V for CAT. IV and 600V for CAT. III or lower categories.

#

CAUTION

The measurable conductor size is max. 110mm in diameter.

Accurate results cannot be obtained if the clamp sensor is not

closed firmly.

When disconnecting the output terminal from the measuring

instrument, do so by removing the plug first and not by pulling

the cord.

6-1 Measuring method

(1) Connect the output terminal to the input terminal on the

measuring instrument.

(2) Power on the measuring instrument.

(3) Press the Joint according to the following illustrations and

unlock it.

(4) Clamp onto one conductor under the test. Locate the conductor

to the position as shown in the below figure. When connecting

the Clamp sensor with our Power meter (MODEL6315 etc.),

check the direction of the Guide arrow mark indicating the

current flowing direction marked on the Joint of the Clamp

sensor to make the phase of the current under test and output

voltage synchronized.

(5) Confirm that the Joint on the Clamp sensor is firmly locked.

● Jointed part of the Clamp sensor may be disconnected if

excessive force is applied to.

● Clamp onto one conductor only; measurements cannot be made

when clamping single-phase (2-wire) or three-phase (3-wire) at

the same time.

6-2 Connecting with Power meter (KEW6315/KEW6310/KEW6305/

MODEL6300)

When this clamp sensor is detected by the auto-detection function

of our KEW6310/ 6315 Power meter after the connection, the type

of the clamp sensor will be displayed as follows. On KEW6310, the

displayed model name will not be “KEW8130”, however, this is

not a malfunction. Enter the model name according to the following

table if setting the type of the clamp sensor directly.

Power meter

Model name displayed through

the auto-detection function

KEW6310

MODEL8124

KEW6315

MODEL8124/8130

● MODEL6300/ KEW6305 does not detect the connected clamp

sensors automatically. Enter the model name directly:

MODEL8124 (1000A).

● For the detailed setting of the clamp sensor, please refer to the

instruction manual for each Power meter.

6-3 Connecting with Logger (KEW5010/5020)

When using this clamp sensor together with our KEW5010 / 5020

Logger;

(1) Connect the clamp sensor to

CH1 of KEW5010/ 5020 while

KEW5010 / 5020 is in powered

off status.

(2) Then power on KEW5010 /

5020. Time will be displayed,

and then

and “1000A”

will be displayed. (KEW5010/

5020 checks the connected

clamp sensors when it is

powered on, and detects and

displays the clamp sensor type and a proper range

automatically.)

(3) Now the instrument is ready for

measurements. When “

(no

connection) is displayed on the

LCD; it means no clamp sensor is

connected to the selected channel

or the connection is loose.

In this case, check the connection and reconnect the clamp

sensor,and power off KEW5010 / 5020. Then power it on again.

* Only KEW5010 / 5020 which have the following or later serial

number may be used with this clamp sensor.

KEW5010: No.8031560 or later

KEW5020: No.8029792 or later

Instruction Manual

FLEXIBLE CLAMP SENSOR

POWER CLAMP SENSOR Series

KEW 8130

03-14 92-2177

DISTRIBUTOR

Kyoritsu reserves the rights to change specifications or designs
described in this manual without notice and without obligations.

Joint part of the sensor

Clamp sensor

Cable

Circuit box

Power indicator

Output cable

Output terminal

3.0 to 5.5V

3.0 to

5.5V

COM(Output Lo)

Output(Hi)

N.C.

N.C.

2. Unlock

1. Press

Joint

Sensor

Lock

Cable

Reference test position of the conductor

for KEW8130 clamp sensor

Load

Source

Guide arrow mark

Reference position
of the conductor