8 Replacement of the separate primary head
Switch off power source before commencing work !
1) Note down terminal assignment before dismantling the ”old” primary head.
2) Install the new primary head as described in the supplied installation instructions.
3) Make electrical connection at the signal converter as described in the installation and
operating instructions for the signal converter.
4) Specific calibration data are defined during factory calibration for each primary head,
which are indicated on the instrument nameplate.
This includes the primary constant GK and the magnetic field frequency. These data
need to be reset in the signal converter.
5) If the size of primary head is also different from the old one, the full-scale range Q
100%
and the
meter size will need to be reset.
6) After resetting the signal converter, carry out a zero point check.
7) If necessary, reset the internal electronic totalizer of the signal converter.
9 Technical data
Meter sizes
IFM 4010 K, IFM 4020 K, IFM 4080 K
DN 10 - 1000 and
3
/
8
” -
0
40”
IFS 4000 F
DN 10 - 3000 and
3
/
8
” - 120”
IFS 4005 F
DN 50 - 1000 and 2” -
0
40”
Pipe flanges
to DIN 2501 (=BS 4504)
DN 10-50 and DN 80 / PN 40
DN 65 and DN 100-150 / PN 16
DN 200-1000 / PN 10
DN 1100-2000 / PN 6
DN 2200-3000 / PN 2.5
to ANSI B 16.5
3
/
8
” -
0
24” / Class 150 lb / RF
to AWWA
14”-120” / Class B or D / FF
Electrical conductivity
≥
0
5
µ
S/cm,
≥
20
µ
S/cm for demineralized cold water
Temperatures
Ambient temperature
Process temperature
Compact systems
-25 to +
1
60 °C
-25 to
≤≤
+
1
60 °C
-13 to +140 °F
-13 to
≤≤
+140 °F
-25 to +
1
40 °C
-25 to
≤≤
+140 °C
*
-13 to +104 °F
-13 to
≤≤
+284 °F
*
IFS 4000 F / IFS 4005 F
-25 to +
1
60 °C
-25 to
≤≤
+180 °C
*
-13 to +140 °F
-13 to
≤≤
+356 °F
*
*
dependent on liner, flange standard, etc.
Max. allowable operating data
Process temperature, operating pressure and
vacuum load for the liner, refer to Section 11
”Limits”