beautypg.com

Electrical connections, 3 supply voltage – KROHNE OPTIWAVE 7300C ATEX EN User Manual

Page 16

background image

3

ELECTRICAL CONNECTIONS

16

OPTIWAVE 7300 C

www.krohne.com

06/2010 - 4000091504 - AD ATEX OPTIWAVE 7300 R06 en

3.5.2 Maximum intrinsically-safe values for the electrical circuit

Level transmitter with the 4...20 mA output option (output terminal 1 or 2)

• U

i

≤30 V

• I

i

≤300 mA

• P

i

≤1 W

• C

i

=30 nF

• L

i

=0.2 mH

Level transmitter with the PROFIBUS PA or FOUNDATION™ Fieldbus output option
(output terminal 1)

• U

i

≤30 V

• I

i

≤300 mA

• P

i

≤1 W

• C

i

=1.6 nF

• L

i

=0 mH

Level transmitter with the PROFIBUS PA or FOUNDATION™ Fieldbus output option
(output terminal 2)

• U

i

≤17.5 V

• I

i

≤380 mA

• P

i

≤5.32 W

• C

i

=3.8 nF

• L

i

=2.2 mH

3.5.3 Supply voltage

Level transmitter with the 4...20 mA output option

Level transmitter with the PROFIBUS PA or FOUNDATION Fieldbus output options

INFORMATION!
The optional second output is galvanically isolated from the main power supply, output 1 and
parts of the device that are grounded.

Current output terminal

Minimum voltage at output

terminal [VDC]

Maximum voltage at output

terminal [VDC]

1 (U

S1

)

14

1

30

1

2 (U

S2

)

2

10

1

30

1

1 Minimum voltage at output terminal for a current output of 22 mA
2 Optional. Use a second power supply. This power supply energizes current output terminal 2 only.

Power supply terminal

Minimum voltage at output

terminal [VDC]

Maximum voltage at output

terminal [VDC]

24 Vdc (U

S1

)

18

30