2.8 Electrical data

Limit switch TG21

The built-in intrinsically safe NAMUR limit switch TG21 may only be connected to isolation
switching amplifiers with separated intrinsically safe circuits to EN 60947 -5 -6 with the
following max. values:

Maximum values of the power supply units

When connecting to intrinsically safe circuits, take into consideration the following maximum
values per circuit for the energy stores.

Limit switch MS14

Built-in limit switch MS14 may only be connected to separate intrinsically safe circuits with the
following maximum values:

When connecting to intrinsically safe circuits, take into consideration the following maximum
values per circuit for the energy stores.

Supply

P

i

[mW]

U

i

[V]

I

i

[mA]

Type 1

34

16

25

Type 2

64

16

25

Type 3

169

16

52

C

i

[nF]

L

i

[µH]

165

150

P

i

[W]

U

i

[V]

I

i

[mA]

1

30

100

C

i

[nF]

L

i

[µH]

0

0