ELECTRICAL CONNECTIONS

20

OPTIFLEX 2200 C/F

www.krohne.com

04/2013 - 4000861902 - AD IECEX OPTIFLEX2200 R02 en

Equipment needed (not supplied)

• 2.5 mm Allen wrench.

• De-energize the circuit.
• After the time given in the table that follows, remove the cover stop 1.

i

Use a 2.5 mm allen wrench.

• Remove the terminal compartment cover 2.

Ex d ia- or Ex ia tb-approved devices:
Time for the internal temperature of the housing to decrease to a safe level

3.2.2 How to close the terminal compartment

Ex i applications

• Attach the terminal compartment cover 2. Turn the terminal compartment cover carefully to

prevent damage to the thread and the gasket.

• Make sure that the terminal compartment cover is tight.

Ex d / Ex t applications

• Attach the terminal compartment cover 2. Turn the terminal compartment cover carefully to

prevent damage to the thread and the gasket.

• Make sure that the terminal compartment cover is tight.
• Use a 2.5 mm Allen wrench to attach the cover stop 1.
• Make sure that the cover stop 1 screw is tight.

INFORMATION!
Ex i applications

Ex i applications

Ex i applications

Ex i applications
If you remove the terminal compartment cover, the device has a degree of ingress protection
IP 20.

WARNING!
Ex d / Ex t applications

Ex d / Ex t applications

Ex d / Ex t applications

Ex d / Ex t applications
Do not remove the terminal compartment cover while the electrical power is connected.

Temperature class

Time for the internal temperature of the housing to

decrease to a safe level

[minutes]

T6, T5

10

T4, T3, T2

Not necessary

DANGER!
Ex d / Ex t applications

Ex d / Ex t applications

Ex d / Ex t applications

Ex d / Ex t applications
Make sure that the terminal compartment is correctly sealed. An explosion can cause death or
injury to personnel and/or damage to equipment. Obey the instructions that follow: