ALTOFLUX 2W IFM 4042 K - EEx

1.2 Data

plates


IFM 4042 K-EEx, type "EEx de [ib]"

IFM 4042 K-EEx, type "EEx de"

1.3 Primary

head

The primary head is the measuring unit of the IFM 4042 K-EEx compact flowmeter and contains
two field coils (see table below for the type of protection) and two electrodes in type of
protection intrinsic safety category "ib" according to EN 50020.

Meter size

Type of protection

DN 10 up to DN 150

Housing:

Encapsulation "m" according to EN 50028 and

increased safety “e” according to EN 50 019

Electrodes:

Intrinsic safety "ib" according to EN 50020

DN 200 up to DN 300

Housing:

Powder filling “q” according to EN 50017 and

increased safety “e” according to 50 019

Electrodes:

Intrinsic safety "ib" according to EN 50020

DN 350 and larger

Field coils:

Increased safety "e" according to EN 50019

Electrodes:

Intrinsic safety "ib" according to EN 50020


NOTE


The intrinsically safe electrode circuits of the IFM 4042 K-EEx compact flowmeter
are only internal circuits and not accessible for the customer.