beautypg.com

Device description, 6 ambient temperature / temperature classes, 7 electrical data – KROHNE OPTIBAR P 2010 C Ex EN User Manual

Page 7

background image

DEVICE DESCRIPTION

2

7

OPTIBAR P 1010/2010 C

www.krohne.com

01/2014 - 4002866801 - AD OPTIBAR PX010 Ex R01en

2.6 Ambient temperature / temperature classes

Use in zone 0 / zone 20

zone 0 / zone 20

zone 0 / zone 20

zone 0 / zone 20, ambient temperature range: -20...+60°C / -4...+140°F

(P

atm

: 0.8...1.1 bar / 11.6...15.9 psi)

Use from zone 1 / zone 21

zone 1 / zone 21

zone 1 / zone 21

zone 1 / zone 21, ambient temperature range: -20...+70°C / -4...+158°F

2.7 Electrical data

Signal output: 4...20 mA, 2-wire
Nominal voltage: 10...28 VDC
Nominal current: 4...20 mA

Built-in equipment for the pressure transmitters may only be connected to separate intrinsically
safe circuits with the following maximum values:

• U

i

[V]: 28 V

• I

i

[mA]: 93 mA

• P

i

[mW]: 660 mW

• C

i

[nF]: ~ 0 nF

• L

i

[µH]: ~ 0 µH

The supply connections have a maximum internal capacity of 27 nF to the housing plus circuit
inductivities 1 µH/m and circuit capacities 160 pF/m (for factory cable).

This manual is related to the following products: