An associated characteristic is the value PFD

avg

(average Probability

of dangerous Failure on Demand). It is dependent on the test interval
T

Proof

between the function tests of the protective function.

Number values see chapter "Safety-related characteristics".

If the "low demand rate" does not apply, the measuring system as
safety-relevant subsystem in "high demand mode" should be used
(IEC 61508-4, 3.5.12).

The fault tolerance time of the complete system must be higher than
the sum of the reaction times or the diagnostics test periods of all
components in the safety-related measurement chain.

An associated characteristic is the value PFH (failure rate).

Number values see chapter "Safety-related characteristics".

The following assumptions form the basis for the implementation of
FMEDA:

l

Failure rates are constant, wear of the mechanical parts is not
taken into account

l

Failure rates of external power supplies are not taken into account

l

Multiple errors are not taken into account

l

The average ambient temperature during the operating time is
40 °C (104 °F)

l

The environmental conditions correspond to an average industrial
environment

l

The lifetime of the components is around 8 to 12 years (IEC 61508-
2, 7.4.7.4, remark 3)

l

The repair time (exchange of the measuring system) after an
nondangerous malfunction is eight hours (MTTR = 8 h)

l

The processing unit can interprete "fail low" and "fail high" failures
as errors and trigger a suitable error message

l

The scanning interval of a connected control and processing unit
is max. 1 hour, in order to react to dangerous, detectable errors

The measuring system should be used appropriately taking pressure,
temperature, density and chemical properties of the medium into
account.

The user-specific limits must be kept. The specifications of the
operating instructions manual must not be exceeded.

Keep in mind when using as dry run protection:

l

Avoid buildup on the vibrating system (probably shorter proof test
intervals will be necessary)

l

Avoid solids > 5 mm (0.2 in) stored in the medium

l

Avoid foam generation with a density of > 0.5 g/cm³ (0.018 lbs/in³)

High demand mode

Assumptions

General instructions and
restrictions

6