beautypg.com

KROHNE OPTISWITCH 5xx0C Contactless SIL EN User Manual

Page 9

background image

Sensor type

Type A

Overflow protection

(max./A-operation)

Dry run protection

(min./B-operation)

SFF

88 %

88 %

PFD

avg

T

Proof

=

1 year

T

Proof

=

5 years

T

Proof

=

10 years

<

0.015 x 10

-2

<

0.072 x 10

-2

<

0.145 x 10

-2

<

0.015 x 10

-2

<

0.073 x 10

-2

<

0.147 x 10

-2

PFH

<

0.033 x 10

-6

/h

<

0.034 x 10

-6

/h

The chronological sequence of PFD

avg

is nearly linear to the operating

time over a period up to 10 years. The above values apply only to the
T

Proof

interval after which a recurring function test must be carried out.

1

5

10

T

Proof

PFD

avg

1

2

3

4

Fig. 1: Chronological sequence of PFD

avg

(figures see above charts)

1

PFD

avg

= 0

2

PFD

avg

after 1 year

3

PFD

avg

after 5 years

4

PFD

avg

after 10 years

Multiple channel architecture

If the measuring system is used in a multiple channel architecture, the
safety-relevant characteristics of the selected structure of the meas.
chain must be calculated specifically for the selected application
according to the above failure rates.

A suitable Common Cause Factor must be taken into account.

Time-dependent proc-
ess of PFD

avg

Specific characteristics

OPTISWITCH series 5000 • - contactless electronic switch

9

1 Functional safety

32746

-

EN

-

100128