1 functional safety, 1 in general, 1functional safety – KROHNE OPTISWITCH 5xx0C Contactless SIL EN User Manual
Page 3
1
Functional safety
1
.1 In general
This safety manual applies to measuring systems consisting of the
vibrating level switch OPTISWITCH series 5000 with integrated
oscillator SWE60C:
OPTISWITCH 5100 C, 5150 C, 5200 C, 5250 C
For instruments with enamelled fork, oscillator SWE60C.E or
SWE
60C.E1 is required.
The measuring system can be implemented for level detection (of
liquids) which meets the special requirements of safety technology.
This is possible up to SIL2 in a single channel architecture (1oo1D),
and up to SIL3 in a multiple channel, redundant architecture.
The SIL declaration of conformity can be downloaded from our
homepage in the Internet.
SIL
Safety Integrity Level
HFT
Hardware Fault Tolerance
SFF
Safe Failure Fraction
PFD
avg
Average Probability of dangerous Failure on Demand
PFH
Probability of a dangerous Failure per Hour
FMEDA
Failure Mode, Effects and Diagnostics Analysis
λ
sd
Rate for safe detected failure
λ
su
Rate for safe undetected failure
λ
dd
Rate for dangerous detected failure
λ
du
Rate for dangerous undetected failure
DC
S
Diagnostic Coverage of safe failures; DC
S
=
λ
sd
/(λ
sd
+
λ
su
)
DC
D
Diagnostic Coverage of dangerous failures; DC
D
=
λ
dd
/(λ
dd
+
λ
du
)
FIT
Failure In Time (1 FIT = 1 failure/10
9
h)
MTBF
Mean Time Between Failure
MTTF
Mean Time To Failure
MTTR
Mean Time To Repair
Further abbreviations and terms are stated in IEC 61508-4.
Scope
Area of application
SIL conformity
Abbreviations, terms
OPTISWITCH series 5000 • - contactless electronic switch
3
1 Functional safety
32746
-
EN
-
100128