5 Connecting to voltage supply

5.1 Preparing the connection

Generally not the following safety instructions:

l

Connect only in the complete absence of line voltage

In hazardous areas you should take note of the appropriate

regulations, conformity and type approval certificates of the

sensors and power supply units.

Connect the power supply according to the following diagrams.

Oscillator SWE60R is designed in protection class 1. To

maintain this protection class, it is absolutely necessary that

the ground conductor be connected to the internal ground

terminal. Take note of the general installation regulations. As a

rule, connect OPTISWITCH 5200 C, 5250 C to vessel ground

(PA), or in case of plastic vessels, to the next ground potential.

On the side of the housing there is a ground terminal between

the cable entries. This connection serves to drain off electro-

static charges. In Ex applications, the installation regulations

for hazardous areas must be given priority.
The data for power supply are stated in the "Technical data" in

the "Supplement".

OPTISWITCH 5200 C, 5250 C is connected with standard

cable with round cross-section. An outer cable diameter of

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable

entry.
If cable with a different diameter or wire cross section is used,

exchange the seal or use an appropriate cable connection.

In hazardous areas, only use approved cable connections for

OPTISWITCH 5200 C, 5250 C.

Take note of the corresponding installation regulations for Ex

applications.

5.2 Connection steps

With Ex instruments, the housing cover may only be opened if

there is no explosive atmosphere present.

Proceed as follows:

Note safety instructions

Take note of safety

instructions for Ex

applications

Select power supply

Selecting the connection ca-

ble

Select connection

cable for Ex applica-

tions

16

OPTISWITCH 5200 C, 5250 C - with relay output

Connecting to voltage supply

30431

-EN
-060831