7 Maintenance and fault rectification
7.1 Maintenance
When used as directed in normal operation, OPTISWITCH
5200 C, 5250 C is completely maintenance free.
7.2 Rectify faults
OPTISWITCH 5200 C, 5250 C offers maximum reliability.
Nevertheless faults can occur during operation. These may be
caused by the following, e.g.:
l
Sensor
l
Process
l
Power supply
l
Signal processing
The first measure to be taken is to check the output signal. In
many cases, the causes can be determined this way and the
faults rectified.
?
OPTISWITCH 5200 C, 5250 C signals "covered" when the
vibrating element is not submerged (overfill protection)
?
OPTISWITCH 5200 C, 5250 C signals "uncovered" when
the vibrating element is submerged (dry run protection)
l
Supply voltage too low
à
Check the power supply
l
Electronics defective
à
Push the characteristics reversal switch. If the instru-
ment then changes the mode, the instrument may be
mechanically damaged. Should the switching function
in the correct mode still be faulty, return the instrument
for repair.
à
Push the characteristics reversal switch. If the instru-
ment then does not change the mode, the oscillator
may be defective. Exchange the oscillator.
l
Unfavourable installation location
à
Mount the instrument at a location in the vessel where
no dead zones or air bubbles can form.
Causes of malfunction
Fault rectification
Checking the switching signal
22
OPTISWITCH 5200 C, 5250 C - with NAMUR output
Maintenance and fault rectification