KROHNE OPTISWITCH 5100C Namur EN User Manual
Page 25
Surface quality
- Standard
R
a
approx. 3 µm (approx. 1.18
-4
in)
- Hygienic version 3A (OPTISWITCH
5150 C)
R
a
<0.8 µm (<3.15
-5
in)
Process fittings
- Thread
G¾ A, ¾ NPT, G1 A, 1 NPT
- Flanges
DIN from DN 25, ANSI from 1"
- hygienic fittings
Bolting DN 40 PN 40, Tri-Clamp 1", Tri-Clamp
1½" PN 10, conus DN 25 PN 40, Tuchenhagen
Varivent DN 50 PN 10
High voltage test (enamel)
max. 5 KV
Gas-tight leadthrough (optional)
- leakage rate
<10
-6
mbar l/s
- pressure resistance
PN 64
- hygienic fittings
Bolting DN 40 PN 40, Tri-Clamp 1", Tri-Clamp
1½" PN 10, conus DN 25 PN 40, Tuchenhagen
Varivent DN 50 PN 10
Output variable
Output
Two-wire NAMUR output
Current consumption
- falling characteristics
>=2.2 mA uncovered/<=1 mA covered
- rising characteristics
<=1 mA uncovered/>=2.2 mA covered
- Fault signal
<=1.0 mA
Necessary processing system
NAMUR processing system according to
IEC 60947-5-6 (EN 50227/DIN 19234)
Modes (NAMUR output adjustable to falling or rising characteristics)
- min.
rising characteristics (High current when im-
mersed)
- max.
falling characteristics (Low current when im-
mersed)
Measuring accuracy
Hysteresis
approx. 2 mm (0.08 in) with vertical installation
Integration time
approx. 500 ms
Frequency
approx. 1200 Hz
OPTISWITCH 5100 C, 5150 C - with NAMUR output
25
Supplement
30429
-EN
-060831