The following instrument combinations meet the requirements

acc. to WHG:
OPTISWITCH 5100 C, 5150 C EX with

l

Oscillator SWE60Z EX

l

signal conditioning instrument SU 501 (Ex) or PLC

The following instrument combinations meet the requirements

according to SIL:
OPTISWITCH 5100 C, 5150 C EX

l

Oscillator SW E60Z (EX)

l

signal conditioning instrument SU 501 (Ex)

The recurring test according to WHG and the function test

according to IEC 61508 can be carried out by pushing the test

key on the signal conditioning instrument or by briefly (> 2

seconds) interrupting the cable to the sensor. The correct

sequence of the switching conditions must be monitored via

the two signal lamps on the signal conditioning instrument as

well as the connected systems. The sensor must neither be

removed nor must a response be triggered by filling the vessel.

This applies to OPTISWITCH 5100 C, 5150 C with two-wire

oscillator SW E60Z EX.
If you are subject to the WHG regulations, you can carry out

the function test with the outputted current values also directly

via a PLC or a process control system.
The implementation and switching sequence of the function

test is described also in the operating instructions manual of

the appropriate signal conditioning instrument.

A function test can be carried out for measuring systems in

conjunction with the two-wire oscillator SW E60Z EX. For this

the integration time must be set to 0.5 s. The signal

conditioning instrument has an integrated test key. The test

key is recessed in the front plate of the signal conditioning

instrument. Push the test key for > 2 seconds with a suitable

object (screwdriver, pen, etc.).
For WHG the following is also applicable: If OPTISWITCH

5100 C, 5150 C is connected to a processing system or a PLC,

you have to interrupt the connection cable to the sensor for > 2

seconds.
After releasing the test key or interrupting the connection cable

to the sensor, the complete measuring system can be checked

WHG

SIL

Recurring test and function

test

Test key on the signal con-

ditioning instrument

22

OPTISWITCH 5100 C, 5150 C - with two-wire output

Set up