beautypg.com

KROHNE OPTISWITCH 3100C NAMUR EN User Manual

Page 22

background image

sequence of the switching conditions must be monitored via

the switching amplifier as well as the connected systems. The

sensor must neither be removed nor response must be

triggered by filling the vessel. This applies to OPTISWITCH

3100 C with NAMUR oscillator VBE60N.
You can carry out the function test with the outputted current

values also directly with a safety PLC or a process control

system.

For measurement setups in conjunection with the NAMUR

oscillator VBE60N, a function test can be carried out. The

integration time must be set to 0.5 s. OPTISWITCH 3100 C

has an integrated simulation key. The simulation key is

lowered on the oscillator. Push the simulation key for >2

seconds.
If OPTISWITCH 3100 C is connected to an SPLC, you have to

interrupt the connection cable to the sensor for >2 seconds.
After releasing the simulation key or briefly interrupting the

connection cable to the sensor, you can check the complete

measuring system on correct function. A switching procedure

is simulated during the test.

2,2

I/mA

1

3

4,5

t/s

1

2

Fig. 14: Flow chart of the function test

1

Full signal

2

Empty signal

Check if all the switching conditions occur in the correct

sequence and the stated time period. If this is not the case,

there is a fault in the measuring system. Keep in mind that

connected instruments are activated during the function test.

This allows you to check the correct function of the measuring

system.

Simulation key on the elec-

tronics module

22

OPTISWITCH 3100 C - with NAMUR output

Set up

31356

-EN
-060830