3 function chart – KROHNE OPTISWITCH 3100C NAMUR EN User Manual

Page 20

background image

light-weight solids, turn the potentiometer to the left stop

(>0.008 g/cm³ or >0.0003 lbs/in³). OPTISWITCH 3100 C will

thus be more sensitive and can detect light-weight solids more

reliably.
For instruments detecting solids in water, these values are not

applicable. The potentiometer is preset and must not be

changed.

The characteristics reversal can be carried out with the DIL

switch. You can choose between falling characteristic curve

(switch position max.) and rising characteristic curve (switch

position min.). This allows you to output the desired current.
Modes

l

min. - rising characteristic curve (High current when

immersed)

l

max. - falling characteristics (Low current when immersed)

The NAMUR output can be switched over to falling or rising

characteristics (see also "Function chart").

The simulation key is located in a recess on the upper side of

the oscillator. Push the simulation key with a suitable object

(screwdriver, pen, etc.).
When the key is pushed, a line break between sensor and

processing unit is simulated. The signal lamp on the sensor

extinguishes. The measuring system must signal a fault and

take on a safe condition when the key is pushed.
Keep in mind that the connected (downstream) instruments will

be activated during operation. This allows you to check the

correct function of the measuring system.

Control lamp (LED) for indication of the switching condition

l

yellow = High current >= 2.2 mA

l

dark = Low current <=1 mA

l

yellow (flashing) = Failure <=1 mA

6.3 Function chart

OPTISWITCH 3100 C level switch

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Characteristics reversal (2)

Simulation key (3)

Signal lamp (6)

20

OPTISWITCH 3100 C - with NAMUR output

Set up