mode acc. to the "Function chart" (max. - max. detection or

overfill protection, min. - min. detection or dry run protection).
We recommend connecting acc. to the quiescent current

principle (contactless electronic switch is open when the

switching point is reached) because the contactless electronic

switch takes on the same (safe) condition if a failure is

detected.

Control lamp for indication of the switching condition.

l

green = switch closed

l

red = switch open

l

red (flashing) = failure

6.3 Function chart

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Level

Switching status

Control lamp

Mode max.

Overfill protection

2

1

Switch closed

Green

Mode max.

Overfill protection

2

1

Switch open

red

Mode min.

Dry run protection

2

1

Switch closed

Green

Mode min.

Dry run protection

2

1

Switch open

red

Failure of the supply voltage

(min./max. mode)

any

2

1

Switch open