beautypg.com

KROHNE OPTISOUND 3010C 4wire EN User Manual

Page 39

background image

Process conditions
Vessel pressure

-20 … 200 kPa (-0.2 … 2.0 bar/-2.9 … 29 psi)

Process temperature (transducer tem-

perature)

-40 … +80°C (-40 … +176°F)

Vibration resistance

mechanical vibrations with 4 g and 5 … 100 Hz

5)

Electromechanical data
Cable entry
- Double chamber housing

l

1x cable entry M20x1.5 (cable-ø 5 … 9 mm),

1x blind stopper M20x1.5

or:

l

1x closing cap ½ NPT, 1x blind stopper

½ NPT

Spring-loaded terminals

for wire cross sections up to 2.5 mm²

Indicating and adjustment module
Power supply and data transmission

through sensor via gold-plated sliding contacts

(I²C bus)

Indication

LC display in full dot matrix

Adjustment elements

4 keys

Protection
- unassembled

IP 20

- mounted into the sensor without

cover

IP 40

Materials
- Housing

ABS

- Inspection window

Polyester foil

Supply voltage
Supply voltage
- non-Ex and Exd instrument

20 … 72 V DC, 20 … 253 V AC, 50/60 Hz

Power consumption

max. 4 VA; 2.1 W

Electrical protective measures
Protection

IP 66/IP 67

Overvoltage category

III

Protection class

I

5)

Tested acc. to the regulations of German Lloyd, GL directive 2

OPTISOUND 3010 C - 4 ... 20 mA/HART - four-wire

39

Supplement

30504

-EN

-050914