ELECTRICAL CONNECTIONS

24

OPTISONIC 3400

www.krohne.com

10/2013 - 7312472200 - AD EX OPTISONIC 3400 -en- R02

4.5 "Ex i" I/O connections

The following intrinsically safe I/O connections are available:

The I/O circuits titled “Ex i I/O” and “Ex i Option” are always provided with type of protection
Intrinsic Safety (Ex ia). The I/O-circuits “Fieldbus I/O Profibus-PA” as well as “Fieldbus I/O
Foundation Fieldbus” can be provided with type of protection Intrinsic Safety.

Up to a maximum of 4 intrinsically safe (Ex ia) in-/outputs are possible. All intrinsically safe
circuits are galvanically isolated with respect to earth and each other. To avoid summation of
voltages and current, the wiring of these “Ex ia”-circuits must be sufficiently separated, e.g. in
accordance with the requirements of standard EN 60079-14, clause 12.2.
The “Ex ia” in-/outputs may only be connected to other “Ex ia” or “Ex ib” approved devices (e.g.
intrinsically safe isolation amplifiers), even if such devices are installed in a non-hazardous
location !

Connection to non-“Ex i” devices, cancels the “Ex ia” properties of the flowmeter.

Terminals L and N (or L+ and L-) for connection of the mains supply are not available with type of
protection “intrinsic safety”. To achieve the necessary separation distances between the non-I.S.
and I.S.according to EN 60079-11 between the non-”Ex i” and “Ex i” circuits, the mains terminals
are provided with a semi-circular protection cover with a “snap-in” lock. This cover MUST be
closed before establishing the power supply to the converter.

I/O PCB

I/O PCB

I/O PCB

I/O PCB

I/O functions

I/O functions

I/O functions

I/O functions

Ex i I/O

Current Output + HART

communication

Pulse / Status Output

Current Output, active +

HART communication

Ex ia IIC

U

i

= 30 V, I

i

= 100 mA, P

i

= 1,0 W

C

i

= 10 nF, L

i

= negligibly low

Ex ia IIC

U

o

= 21 V, I

o

= 90 mA, P

o

= 0,5 W

Lineair characteristics

C

o

= 90 nF, L

o

= 2,0 mH

C

o

= 110 nF, L

o

= 0,5 mH

Ex i Option

Current Output

Pulse / Status Output /

Control Input

Current Output, active

Ex ia IIC

U

i

= 30 V, I

i

= 100 mA, P

i

= 1,0 W

C

i

= 10 nF, L

i

= negligibly low

Ex ia IIC

U

o

= 21 V, I

o

= 90 mA, P

o

= 0,5 W

Lineair characteristics

C

o

= 90 nF, L

o

= 2,0 mH

C

o

= 110 nF, L

o

= 0,5 mH

Fieldbus I/O

Profibus-PA

Foundation Fieldbus

Ex ia IIC

U

i

= 24 V, I

i

= 380 mA, P

i

= 5,32 W

C

i

= 5 nF, L

i

= 10 μH

Suitable for connection to an intrinsically safe

fieldbus in accordance with the FISCO model.

INFORMATION!
For flow converters with an

Ex e

terminal compartment,installed in a Division 2, the non-

incendive terminal compartment can be opened in an energized state for short periods of time,
to access the intrinsically safe terminals for possible checks. However, the semi-circular
insulation cover over the non-intrinsically safe mains supply terminals L and N (or L+ and L-)
MUST be kept closed.